NOTE: SETTINGS ARE MADE THROUGH SUPPLIED POWERCHUTE SOFTWARE OR OPTIONAL SMART SLOT
ACCESSORY CARDS.
FUNCTION | FACTORY | USER SELECTABLE CHOICES | DESCRIPTION | ||
DEFAULT | |||||
|
|
|
| ||
Low Battery Warning. |
| Brightly lit: Low battery | The low battery warning | ||
PowerChute interface |
| warning interval is about two | beeps are continuous when | ||
| minutes. |
| two minutes of run time | ||
software provides auto- |
|
| |||
| Dimly lit: | Low battery | remain. | ||
matic, unattended shut- |
| ||||
| warning interval is about five |
| |||
down when approxi- |
| To change the warning in- | |||
| minutes. |
| |||
mately two minutes (by |
|
| terval default setting, press | ||
| Off: | Low battery | |||
default) of battery oper- |
| the voltage sensitivity button | |||
| warning interval is about | ||||
ated run time remains. |
| (use a pointed object such as | |||
| eight minutes. | ||||
|
| a pen to do so), while press- | |||
|
| Possible interval settings: | |||
|
| ing and holding the | |||
|
| 2, 5, 8, 11, 14, 17, 20, 23 | |||
|
| minutes. |
| button (front panel). | |
|
|
|
| ||
Synchronized | 0 seconds | 60, 120, 180, 240, 300, 360, | The UPS will wait the speci- | ||
Delay |
| 420 seconds | fied time after the return of | ||
|
|
|
| utility power before | |
|
|
|
| (to avoid branch circuit | |
|
|
|
| overload). | |
|
|
|
| ||
High Transfer Point | 230V models: | 230V models: | To avoid unnecessary bat- | ||
| 253VAC | 257, 261, 265VAC | tery usage, set the high | ||
| 120V models: | 120V models: | transfer point higher if the | ||
| utility voltage is chronically | ||||
| 127VAC | 130, 133, 136VAC | |||
| high and the connected | ||||
|
|
|
| ||
| 100V models: | 100V models: | equipment is known to work | ||
| 108VAC | 110, 112, 114VAC | under this condition. | ||
|
|
|
| ||
Low Transfer Point | 230V models: | 230V models: | Set the low transfer point | ||
| 208VAC | 196, 200, 204VAC | lower if the utility voltage is | ||
| 120V models: | 120V models: | chronically low and the con- | ||
| nected equipment can toler- | ||||
| 106VAC | 97, 100, 103VAC | |||
| ate this condition. | ||||
|
|
|
| ||
| 100V models: | 100V models: |
| ||
| 92VAC | 86, 88, 90VAC |
| ||
|
|
|
| ||
Output Voltage | 230V models: | 230V models: | 230V models ONLY, allow | ||
| 230VAC | 220, 240VAC | the user to select the output | ||
|
|
|
| voltage. | |
|
|
|
|
|
7