![High Transfer Point](/images/new-backgrounds/124945/12494521x1.webp)
NOTE: SETTINGS ARE MADE THROUGH THE SUPPLIED POWERCHUTE SOFTWARE OR
THE NETWORK INTERFACE CONNECTION. REFER TO THE SOFTWARE HELP GUIDES FOR DETAILS.
FUNCTION |
| FACTORY | USER SELECTABLE | DESCRIPTION |
| DEFAULT | CHOICES | ||
|
|
| ||
High Transfer Point | 120 V: | 120 V: | If the utility voltage is usually high and the | |
| 127 | VAC | 127, 130, 133, 136 VAC | connected equipment is specified to operate |
| 230 | V: | 230V: | with input voltages this high, set the high |
| transfer point higher to avoid unnecessary | |||
| 253 | VAC | 253, 257, 261, 265 VAC | battery usage. |
|
|
|
| |
Low Transfer Point | 120 V: | 120 V: | If the utility voltage is usually low and the | |
| 106 | VAC | 106, 103, 100, 97 VAC | connected equipment is specified to operate |
| 230 | V: | 230 V: | with input voltages this low, set the low |
| transfer point lower. | |||
| 208 | VAC | 208, 204, 200, 196 VAC |
|
|
|
|
|
|
9