Parameter Settings

4.0 Parameter Settings

Below tables show operating parameters programmable from keyboard. Only qualified users should alter programming parameters. See below examples.

Parameter Settings

Parameter

Setting*

 

Comments

 

 

 

 

 

 

 

 

Bypass operation

YES, NO

YES will switch the system into

 

 

bypass mode***

 

 

 

 

 

 

 

 

Language

GB, D, F, DK, S, SF, NL, PL, CZ,

Languages of text in display

 

E, P, SK, H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Autostart

YES, NO

Automatic restart by mains return

 

 

(1 min. delay). Ensures quick

 

 

battery recharge.

 

 

 

 

 

 

 

 

Remote shutdown active

YES, NO

Shutdown of UPS by remote

 

 

signal when in battery operation.

 

 

Saves battery energy.

 

 

 

 

 

 

 

 

Remote shutdown

HIGH, LOW

Nature of remote shutdown

 

 

signal level

 

 

 

 

 

 

 

 

 

 

 

Remote shutdown time

0, 1, 2, 3, 4, 5, 6, 7, 8, 9, 10 min.

Time delay on remote shutdown

 

 

of UPS

 

 

 

 

 

 

 

 

 

 

 

Battery capacity test

Initiates back-up time check.

 

 

Time measured from start until it

 

 

reaches low DC warning level

 

 

(See User Guide, section 6).

 

 

 

 

 

 

 

Battery monitor test **

Initiates checks of battery

 

 

condition by 25% discharging.

 

 

 

 

 

 

 

Automatic battery test**

OFF, 3,6 months

Activates the battery monitor test

 

 

in cyclic intervals.

 

 

 

 

 

 

 

 

 

 

Battery monitor reset**

Press the

 

 

and

 

 

key to

 

 

 

 

 

reset alarm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(flashing light).

 

 

 

 

 

 

 

 

 

 

 

Boost charge

YES, NO

YES results in boost charge (10

 

 

hours)

 

 

 

 

 

 

 

 

 

 

 

Autoboost charge

YES, NO

YES results in boost charge after

 

 

battery operation (10 hours).

 

 

 

 

 

 

 

 

Enter new date

YYMMDD

Set to local date

 

 

 

 

 

 

 

 

Enter new time

HHMMSS

Set to local time (24 hour clock)

 

 

 

 

 

 

 

 

 

*Factory settings in bold

**For systems with active Battery Monitor only

***Do not leave system running in bypass mode (Static bypass) for extended periods of time, as batteries are not recharged in bypass mode.

990-4055

User Guide APC Silcon 120-160kW 400V UPS

21