Installation

Location

Requirements

> 500

(20)

>

500 (20)

 

 

 

Dimensions are shown in mm (in).

na3362a

When deciding where to locate the cooling unit, consider cooling needs, air flow, and the location of the electrical outlet. The cooling unit can be no more than 2.4 m (8 ft) from the electrical outlet, condenser intake and exhaust access.

Cooling needs. Position the cooling unit as close as possible to the main heat source that requires cooling.

Air flow. Position the rear of the cooling unit at least 500 mm (20 in) away from a wall or other equipment.

Location of electrical outlet. Place the cooling unit no farther than 2.4 m (8 ft) from a dedicated 120V, 60Hz, 15A branch circuit receptacle.

Electrical Hazard: Do not use extension cords with this equipment. Using an extension cord reduces circuit protection and will void the warranty.

Caution: To help avoid loss of cooling, only connect this equipment to a single-outlet dedicated circuit.

InRoom SC 60 Hz User Manual

9