Managing the Unit with SNMP

Using the OIDs

Using monitoring

Use the read-only [mUpsEnviron] OIDs to view temperature and

OIDs

humidity values.

 

 

 

 

 

OID

Function

 

 

 

 

mUpsRelativeHumidity

Reports the relative humidity sensed by the probes.

 

 

 

 

mUpsAmbientTmperature

Reports the ambient temperature in Celsius, sensed

 

 

by the probes.

 

 

 

Using contact OIDs Use the [mUpsContact] OIDs to view and configure the current contact sensor values.

OID

Function

 

 

mUpsContactNumContacts

Lists how many contact sensors the unit uses.

 

 

{mUpsContactTable}

Lists the OIDs for each contact sensor:

 

contactNumber: Identifies the contact sensor for

 

which the other OIDs apply.

 

normalState: Defines the contact sensor’s normal

 

condition (unknown, open, or closed).

 

description: Defines the purpose of the contact

 

sensor

 

monitoringStatus: Defines whether the contact

 

sensor is being monitored

 

currentStatus: Identifies the sensor’s current

 

condition (unknown, noFault, or fault).

 

 

Environmental Monitoring Unit: User’s Guide

24

Page 28
Image 28