Compact® NSF and NSJ 150 to 600 A Circuit Breakers
Section 
UL 489 TEST PROCEDURE
Standard Tests For electronic trip circuit breakers and uncompensated 
| Test | 
 | Sequence | 
 | |
| 
 | 
 | X | Y | Z | 
| 200% | Calibration at 25° C (77° F) | ■ | ■ | ■ | 
| 
 | 
 | 
 | 
 | 
 | 
| 135% | Calibration at 25° C (77° F) | ■ | 
 | 
 | 
| 
 | 
 | 
 | 
 | |
| Calibration of Adjustable Instantaneous Trip | ■ | 
 | 
 | |
| 
 | 
 | 
 | 
 | |
| Overload | ■ | 
 | 
 | |
| 
 | 
 | 
 | 
 | |
| Tungsten Lamp Load | ① | 
 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
| 100% | Calibration at 40° C (104° F) | ② | 
 | 
 | 
| 
 | 
 | 
 | 
 | |
| Temperature and 100% Calibration at 25° C (77° F) | ■ | 
 | 
 | |
| 
 | 
 | 
 | 
 | |
| Endurance | 
 | ■ | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
| 200% | Calibration at 25° C (77° F) Repeated | 
 | ■ | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
| 135% | Calibration at 25° C (77° F) Repeated | 
 | ■ | 
 | 
| 
 | 
 | 
 | 
 | |
| Interrupting Ability (Y sequence) | 
 | ■ | 
 | |
| 
 | 
 | 
 | 
 | |
| Interrupting Ability (Z sequence) | 
 | 
 | ■ | |
| 
 | 
 | 
 | 
 | 
 | 
| 200% | Trip Out at 25° C (77° F) | 
 | ■ | ■ | 
| 
 | 
 | 
 | 
 | |
| Dielectric Voltage Withstand | ■ | ■ | ■ | |
①Applies only to circuit breakers rated 50 A or less, and 125 or 125/250 V or less.
②Applies only to 
Standard
Specifications
| Temperature | The temperature rise at the circuit breaker and at its terminals does not exceed specified limits when | |||
| 
 | connected with specified cables or bus bars (see below) and at its rated current. | |||
| 
 | Examples of specified wires and bus: | |||
| 
 | • 75° C Copper Wire | 
 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
| 
 | Rating | Number | Size | 
 | 
| 
 | 100 A | 1 | #1 AWG (60° C) | 
 | 
| 
 | 
 | 
 | 
 | |
| 
 | 1 | #3 AWG | ||
| 
 | 
 | |||
| 
 | 
 | 
 | 
 | 
 | 
| 
 | 250 A | 1 | 250 kcmil | |
| 
 | 
 | 
 | 
 | 
 | 
| 
 | 400 A | 2 | 3/0 AWG | |
| 
 | 
 | 
 | 
 | 
 | 
| 
 | 600 A | 2 | 350 kcmil | |
| 
 | 
 | 
 | 
 | 
 | 
| 
 | 800 A | 3 | 300 kcmil | |
| 
 | 
 | 
 | 
 | 
 | 
| 
 | 1000 A | 3 | 400 kcmil | |
| 
 | 
 | 
 | 
 | 
 | 
| 
 | 1200 A | 4 | 350 kcmil | |
| 
 | 
 | 
 | 
 | 
 | 
•Copper Busbar
| Rating | Number | Size | |
| 1600 A | 2 | 1/4 x 3 | |
| 
 | 
 | 
 | |
| 2000 A | 2 | 1/4 x 4 | |
| 
 | 
 | 
 | |
| 2500 A | 2 | 1/4 x 5 | |
| 
 | 
 | ||
| 4 | 1/4 x  | ||
| 
 | |||
| 
 | 
 | 
 | |
| 3000 A | 4 | 1/4 x4 | |
| 
 | 
 | 
 | 
| 
 | (1200 A or  | 
| Calibration | 200% calibration at 25°  | 
| 
 | from three minutes for 30 A rated circuit breakers to 30 minutes for over 2000 A rated circuit breakers. | 
135% calibration at 25° 