Compact® NSF and NSJ 150 to 600 A Circuit Breakers

Section 13—Supplementary Technical Information

UL 489 TEST PROCEDURE

Standard Tests For electronic trip circuit breakers and uncompensated thermal-magnetic circuit breakers rated 40° C, the test sequences are as shown in the table below:

Test

 

Sequence

 

 

 

X

Y

Z

200%

Calibration at 25° C (77° F)

 

 

 

 

 

135%

Calibration at 25° C (77° F)

 

 

 

 

 

 

Calibration of Adjustable Instantaneous Trip

 

 

 

 

 

 

Overload

 

 

 

 

 

 

Tungsten Lamp Load

 

 

 

 

 

 

 

100%

Calibration at 40° C (104° F)

 

 

 

 

 

 

Temperature and 100% Calibration at 25° C (77° F)

 

 

 

 

 

 

Endurance

 

 

 

 

 

 

 

200%

Calibration at 25° C (77° F) Repeated

 

 

 

 

 

 

 

135%

Calibration at 25° C (77° F) Repeated

 

 

 

 

 

 

Interrupting Ability (Y sequence)

 

 

 

 

 

 

Interrupting Ability (Z sequence)

 

 

 

 

 

 

 

200%

Trip Out at 25° C (77° F)

 

 

 

 

 

Dielectric Voltage Withstand

Applies only to circuit breakers rated 50 A or less, and 125 or 125/250 V or less.

Applies only to thermal-magnetic breakers rated 40° C.

Standard

Specifications

Temperature

The temperature rise at the circuit breaker and at its terminals does not exceed specified limits when

 

connected with specified cables or bus bars (see below) and at its rated current.

 

Examples of specified wires and bus:

 

75° C Copper Wire

 

 

 

 

 

 

 

 

Rating

Number

Size

 

 

100 A

1

#1 AWG (60° C)

 

 

 

 

 

 

1

#3 AWG

 

 

 

 

 

 

 

 

250 A

1

250 kcmil

 

 

 

 

 

 

400 A

2

3/0 AWG

 

 

 

 

 

 

600 A

2

350 kcmil

 

 

 

 

 

 

800 A

3

300 kcmil

 

 

 

 

 

 

1000 A

3

400 kcmil

 

 

 

 

 

 

1200 A

4

350 kcmil

 

 

 

 

 

Copper Busbar

Rating

Number

Size

1600 A

2

1/4 x 3

 

 

 

2000 A

2

1/4 x 4

 

 

 

2500 A

2

1/4 x 5

 

 

4

1/4 x 2-1/2

 

 

 

 

3000 A

4

1/4 x4

 

 

 

 

(1200 A or Less—1000 A / in2)

Calibration

200% calibration at 25° C—the circuit breaker must trip within time limits which depend on the rating

 

from three minutes for 30 A rated circuit breakers to 30 minutes for over 2000 A rated circuit breakers.

135% calibration at 25° C—the circuit breaker must trip within two hours for circuit breakers rated more than 50 A.

© 1995–2003 Schneider Electric All Rights Reserved

67

Page 67
Image 67
Schneider Electric Class 615 dimensions UL 489 Test Procedure, Standard Specifications, Temperature, Calibration