Compact® NSF and NSJ 150 to 600 A Circuit Breakers
Section 
UL 489 Listed Ratings
| 06153061 | Number of Poles | 
 | 
 | 
 | 3, 4, 4 OSN* | 
 | 3, 4 | 
 | 
 | |
| 
 | Compact® Circuit Breakers | 
 | 
 | 
 | NSJ400 | 
 | 
 | NSJ600 | 
 | 
 | 
| 
 | Rated Voltage (V) | 
 | AC 50/60 Hz | 
 | 600 | 
 | 
 | 600 | 
 | 
 | 
| 
 | Rated Current (A) | In | 40° C | 
 | 400 (100% Rated Circuit Breaker) | 600 | 
 | 
 | ||
| 
 | 
 | 
 | 
 | 
 | N | H | L | N | H | L | 
| 
 | Interrupting Ratings (kA rms) | 
 | 
 | 240 V | 65 | 100 | 150 | 65 | 100 | 150 | 
| 
 | 
 | 
 | 
 | 480 V | 35 | 65 | 100 | 35 | 65 | 100 | 
| 
 | 
 | 
 | 
 | 600 Y/ 347 V | — | — | — | — | — | — | 
| 
 | 
 | 
 | 
 | 600 V | 18 | 25 | 25 | 18 | 25 | 25 | 
| 
 | *Oversized Neutral | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 
 | IEC  | 
 | 
 | 
 | 
 | 
 | 
 | 
 | ||
| 06153063 | Compact® Circuit Breakers | 
 | 
 | 
 | NSJ400 | 
 | 
 | NSJ600 | 
 | 
 | 
| Rated Insulation Voltage (V) | Ui | 
 | 
 | 750 | 
 | 
 | 750 | 
 | 
 | |
| 
 | Number of Poles | 
 | 
 | 
 | 3, 4, 4 OSN* | 
 | 3, 4 | 
 | 
 | |
| 
 | Rated Impulse | Uimp | 
 | 8 | 
 | 
 | 8 | 
 | 
 | |
| 
 | Withstand Voltage (kV) | 
 | 
 | 
 | 
 | 
 | ||||
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | Rated Operational Voltage (V) | Ue | AC 50/60 Hz | 
 | 690 | 
 | 
 | 690 | 
 | 
 | 
| 
 | DC | 
 | 500 | 
 | 
 | 500 | 
 | 
 | ||
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |||
| 
 | Rated Current (A) | In | 40° C | 
 | 400 | 
 | 
 | 600 | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
 | N | H | L | N | H | L | 
| 
 | Ultimate Breaking Capacity | Icu | AC 50/50 Hz | 220/240 V | 85 | 100 | 150 | 85 | 100 | 150 | 
| 
 | (kA rms) | |||||||||
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 
 | 
 | 
 | 380/415 V | 45 | 70 | 150 | 45 | 70 | 150 | 
| 
 | 
 | 
 | 
 | 440 V | 42 | 65 | 130 | 42 | 65 | 130 | 
| 
 | 
 | 
 | 
 | 500 V | 30 | 50 | 70 | 30 | 50 | 70 | 
| 
 | 
 | 
 | 
 | 525 V | 22 | 35 | 50 | 22 | 35 | 50 | 
| 
 | 
 | 
 | 
 | 600/690 V | 10 | 20 | 35 | 10 | 20 | 35 | 
| 
 | 
 | 
 | DC | 250 V (1 pole) | — | 85 | — | — | 85 | — | 
| 
 | 
 | 
 | 
 | 500 V (2 pole | — | 85 | — | — | 85 | — | 
| 
 | 
 | 
 | 
 | in series) | ||||||
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | Service Breaking Capacity | Ics | (% Icu) | 
 | 100% | 100% | 100% | 100% | — | 100% | 
| 
 | Utilization Category | 
 | 
 | 
 | A | A | A | A | — | A | 
| 
 | *Oversized Neutral | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| ©  | 9 | 