Compact® NSF and NSJ 150 to 600 A Circuit Breakers
Section
UL 489 Listed Ratings
06153061 | Number of Poles |
|
|
| 3, 4, 4 OSN* |
| 3, 4 |
|
| |
| Compact® Circuit Breakers |
|
|
| NSJ400 |
|
| NSJ600 |
|
|
| Rated Voltage (V) |
| AC 50/60 Hz |
| 600 |
|
| 600 |
|
|
| Rated Current (A) | In | 40° C |
| 400 (100% Rated Circuit Breaker) | 600 |
|
| ||
|
|
|
|
| N | H | L | N | H | L |
| Interrupting Ratings (kA rms) |
|
| 240 V | 65 | 100 | 150 | 65 | 100 | 150 |
|
|
|
| 480 V | 35 | 65 | 100 | 35 | 65 | 100 |
|
|
|
| 600 Y/ 347 V | — | — | — | — | — | — |
|
|
|
| 600 V | 18 | 25 | 25 | 18 | 25 | 25 |
| *Oversized Neutral |
|
|
|
|
|
|
|
|
|
| IEC |
|
|
|
|
|
|
| ||
06153063 | Compact® Circuit Breakers |
|
|
| NSJ400 |
|
| NSJ600 |
|
|
Rated Insulation Voltage (V) | Ui |
|
| 750 |
|
| 750 |
|
| |
| Number of Poles |
|
|
| 3, 4, 4 OSN* |
| 3, 4 |
|
| |
| Rated Impulse | Uimp |
| 8 |
|
| 8 |
|
| |
| Withstand Voltage (kV) |
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
| |
| Rated Operational Voltage (V) | Ue | AC 50/60 Hz |
| 690 |
|
| 690 |
|
|
| DC |
| 500 |
|
| 500 |
|
| ||
|
|
|
|
|
|
|
| |||
| Rated Current (A) | In | 40° C |
| 400 |
|
| 600 |
|
|
|
|
|
|
| N | H | L | N | H | L |
| Ultimate Breaking Capacity | Icu | AC 50/50 Hz | 220/240 V | 85 | 100 | 150 | 85 | 100 | 150 |
| (kA rms) | |||||||||
|
|
|
|
|
|
|
|
|
| |
|
|
|
| 380/415 V | 45 | 70 | 150 | 45 | 70 | 150 |
|
|
|
| 440 V | 42 | 65 | 130 | 42 | 65 | 130 |
|
|
|
| 500 V | 30 | 50 | 70 | 30 | 50 | 70 |
|
|
|
| 525 V | 22 | 35 | 50 | 22 | 35 | 50 |
|
|
|
| 600/690 V | 10 | 20 | 35 | 10 | 20 | 35 |
|
|
| DC | 250 V (1 pole) | — | 85 | — | — | 85 | — |
|
|
|
| 500 V (2 pole | — | 85 | — | — | 85 | — |
|
|
|
| in series) | ||||||
|
|
|
|
|
|
|
|
|
| |
| Service Breaking Capacity | Ics | (% Icu) |
| 100% | 100% | 100% | 100% | — | 100% |
| Utilization Category |
|
|
| A | A | A | A | — | A |
| *Oversized Neutral |
|
|
|
|
|
|
|
|
|
© | 9 |