Compact® NSF and NSJ 150 to 600 A Circuit Breakers
Section 
| Options for | Equipment  | |||
| Electronic Trip | 
 | 
 | 
 | |
| Type | Residual Current | |||
| Unit STR53UP | ||||
| 
 | 
 | 
 | ||
| Tripping threshold | Ig | Adjustable (8 Settings)  | ||
| 
 | ||||
| 
 | 
 | 
 | ||
| 
 | Accuracy | ± 15% | ||
| 
 | 
 | |||
| 
 | 
 | 
 | 
 | |
| 
 | Tripping time (ms) | Max. overcurrent time before tripping (Tg) | Adjustable (4 Settings + Constant I2t Function) 60, 140, 230, 350 | |
| 
 | Total Breaking Time | |||
| 
 | 
 | |||
| 
 | 
 | 
 | 
 | |
Ammeter (I)
| 06153068 | 
 | 
 | 
 | 
| 
 | 
 | 
 | A | 
| In | I1 | I2 | I3 | 
A digital display continuously indicates the current of the phase with the greatest load. By pressing a scroll button, it is also possible to display successively the readings of I1, I2, I3 and I neutral. LEDs indicate the phase for which the current is displayed.
| 
 | A number of circuit breakers are interconnected one after another by a pilot wire. In the event of a | |
| Interlocking (ZSI) | ||
| 
 | • If a given trip unit STR53UP detects the fault, it informs the upstream circuit breaker which applies | |
| 
 | 
 | the set time delay | 
| 
 | • If the trip unit STR53UP does not detect the fault, the upstream circuit breaker trips after its shortest | |
| 
 | 
 | time delay | 
| 
 | In this way, the fault is cleared rapidly by the nearest circuit breaker. In addition, thermal stresses on | |
| 
 | the circuits are minimized and time discrimination is maintained throughout the installation. | |
| 
 | The use of  | |
| Outputs | circuits wired by the user. | |
| Communication | Transmission of the following data to Digipact® distribution monitoring and control modules: | |
| (COM) | • | Settings | 
| 
 | ||
| 
 | • Phase and neutral currents (rms values) | |
| 
 | • Highest current of the three phases | |
| 
 | • | Overload condition alarm | 
| Possible | • | I | 
| Combinations | • | T | 
| 
 | • | I + T | 
| 
 | • | I + COM | 
| 
 | • I + T + COM | |
| 
 | • | ZSI | 
| 
 | • | ZSI + I | 
| 
 | • | ZSI + T | 
• ZSI + I + T
• ZSI + I + COM
• ZSI + I + T + COM