Compact® NSF and NSJ 150 to 600 A Circuit Breakers
Section
UL 489 Listed Ratings
06153061 | Compact® Switches |
| NSJ400A | NSJ600A |
|
| |||
| Number of Poles |
| 3, 4, 4P OSN* | 3, 4 |
| Rated Voltage (V) | AC 50/60 Hz | 600 | 600 |
| Rated Current (A) |
| 400 | 600 |
*Oversized Neutral Protection:
IEC 947-3 Ratings
Compact® Switches |
|
| NSF150A | NSF250A | |
Number of Poles |
|
| 3, 4, 4P OSN* | 3, 4 | |
|
|
|
|
| |
Rated Insulation Voltage (V) | Ui |
| 750 | 750 | |
|
|
|
|
| |
Rated Impulse Withstand | Uimp |
| 8 | 8 | |
Voltage (kV) |
| ||||
|
|
|
| ||
|
|
|
|
| |
Rated Operational Voltage (V) | Ue | AC 50/60 Hz | 690 | 690 | |
|
|
| |||
DC | 500 | 500 | |||
|
| ||||
|
|
|
|
| |
|
| AC23A 690 V | 400 | 630 | |
Rated Operational Current (V) | Ie |
|
|
| |
DC23A 250 V | 400 | 630 | |||
|
|
|
|
| |
|
| DC23A 500 V (2 poles in series) | 400 | 630 | |
|
|
|
|
| |
Making Capacity (kA peak) |
|
| 7.1 | 8.5 | |
|
|
|
|
| |
Icw | Icw (kA rms) | 5 | 8 | ||
|
|
| |||
(kA rms) | Duration (s) | 3 | 3 | ||
| |||||
|
| ||||
|
|
|
|
|
*Oversized Neutral Protection
Short-circuit Withstand Current
Molded case switches are identical to molded case circuit breakers, except they are not equipped with trip units and sensors. Molded case switches open when the handle is switched to the OFF position or in response to an auxiliary tripping device such as a shunt trip or an undervoltage release.
These switches open instantaneously at a
•NSF150/250 A switches: 2000 A
•NSJ 400/600 A switches: 6000 A
These switches are suitable for use on a circuit capable of delivering not more than:
•240 V: 100 kA for NSF switches and 150 kA for NSJ switches
•480 V: 65 kA for NSF switches and 100 kA for NSJ switches
•600 V (600Y/347 for NSF switches): 25 kA
Switches are Listed under UL file E103740 and Certified under CSA file LR 88980.