Compact® NSF and NSJ 150 to 600 A Circuit Breakers
Section 
SECTION 5—SWITCHES 
RATINGS AND INTERRUPTING RATINGS
UL 1087 Listed Ratings
| 06153061 | Compact® Switches | 
 | NSF150A | NSF250A | 
| 
 | 
 | |||
| 
 | Number of Poles | 
 | 3, 4, 4P OSN* | 3, 4 | 
| 
 | Rated Voltage (V) | AC 50/60 Hz | 600Y/ 347 | 600Y/ 347 | 
| 
 | Rated Current (A) | 
 | 150 | 250 | 
*Oversized Neutral Protection: 
IEC 947-3  Ratings
| Compact® Switches | 
 | 
 | NSF150A | NSF250A | |
| Number of Poles | 
 | 
 | 3, 4, 4P OSN* | 3, 4 | |
| 
 | 
 | 
 | 
 | 
 | |
| Rated Insulation Voltage (V) | Ui | 
 | 750 | 750 | |
| 
 | 
 | 
 | 
 | 
 | |
| Rated Impulse Withstand | Uimp | 
 | 8 | 8 | |
| Voltage (kV) | 
 | ||||
| 
 | 
 | 
 | 
 | ||
| 
 | 
 | 
 | 
 | 
 | |
| Rated Operational Voltage (V) | Ue | AC 50/60 Hz | 690 | 690 | |
| 
 | 
 | 
 | |||
| DC | 500 | 500 | |||
| 
 | 
 | ||||
| 
 | 
 | 
 | 
 | 
 | |
| 
 | 
 | AC23A 690 V | 160 | 250 | |
| Rated Operational Current (V) | Ie | 
 | 
 | 
 | |
| DC23A 250 V | 160 | 250 | |||
| 
 | 
 | 
 | 
 | 
 | |
| 
 | 
 | DC23A 500 V (2 poles in series) | 160 | 250 | |
| 
 | 
 | 
 | 
 | 
 | |
| Making Capacity (kA peak) | 
 | 
 | 3.6 | 4.9 | |
| 
 | 
 | 
 | 
 | 
 | |
| Icw | Icw (kA rms) | 2.5 | 3.5 | ||
| 
 | 
 | 
 | |||
| (kA rms) | Duration (s) | 3 | 3 | ||
| 
 | |||||
| 
 | 
 | ||||
| 
 | 
 | 
 | 
 | 
 | 
*Oversized Neutral Protection
| ©  | 17 | 