Compact® NSF and NSJ 150 to 600 A Circuit Breakers
Section 
SECTION 6—MOTOR  CIRCUIT PROTECTORS
RATINGS AND INTERRUPTING RATINGS
UL 489 Recognized Component
| 06153033 | Compact® Circuit Breakers | 
 | 
 | NSF150HC | NSF250HC | 
 | 
| 
 | 
 | 
 | 
 | |||
| 
 | Number of Poles | 
 | 
 | 3 | 3 | 
 | 
| 
 | Rated Voltage (V) | 
 | AC 50/60 Hz | 600Y/347 | 600Y/347 | 
 | 
| 
 | Rated Current (A) | In | 40° C | 150 | 200 | 250 | 
| 
 | Magnetic Trip Setting | Im | 
 | 1000– | 1250– | |
| 
 | 
 | 2000 | 2500 | |||
| 
 | 
 | 
 | 
 | 
 | 
IEC 947-2  and EN 60947-2  Ratings
| Compact® Circuit Breakers | 
 | 
 | 
 | NSF150HC | NSF250HC | 
 | |
| Number of Poles | 
 | 
 | 
 | 3 | 3 | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| Rated Insulation Voltage (V) | Ui | 
 | 
 | 750 | 750 | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| Rated Impulse Withstand | Uimp | 
 | 
 | 8 | 8 | 
 | 
 | 
| Voltage (kV) | 
 | 
 | 
 | 
 | |||
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| Rated Operational Voltage (V) | Ue | AC 50/60 Hz | 
 | 690 | 690 | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 
 | 
 | DC | 
 | 500 | 500 | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| Rated Current (A) | In | 40° C | 
 | 150 | 200 | 
 | 250 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 
 | 
 | 
 | 
 | HC | HC | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| Ultimate Breaking Capacity | Icu | AC 50/60 Hz | 220/240 V | 100 | 100 | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| (kA rms) | 
 | 
 | 380/415 V | 70 | 70 | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 
 | 
 | 
 | 440 V | 65 | 65 | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 
 | 
 | 
 | 500 V | 50 | 50 | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 
 | 
 | 
 | 525 V | 35 | 35 | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 
 | 
 | 
 | 660/690 V | 10 | 10 | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 
 | 
 | DC | 250 V (1 pole) | 85 | 85 | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 
 | 
 | 
 | 500 V (2 poles in series) | 85 | 85 | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| Service Breaking Capacity | Ics | (% Icu) | 
 | 100% | 100% | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| Utilization Category | 
 | 
 | 
 | A | A | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| ©  | 19 | 