
| 
 | Compact® NSF and NSJ 150 to 600 A Circuit Breakers | 
| 
 | Section  | 
| Dielectric | After testing, the circuit breaker must withstand for one minute a voltage of 1000 V plus twice the rated | 
| 
 | voltage between: | 
| 
 | • Line and load terminals with circuit breaker in open, tripped and off positions | 
| 
 | • Terminals of opposite polarity with circuit breaker closed | 
| 
 | • Live parts and the overall enclosure with circuit breaker open and closed | 
| Optional Tests | • High available fault  | 
| 
 | Listing label applied at higher values than the standard; test sequence is as follows: | 
—200% calibration
—Interrupting capacity: an opening operation followed by a 
The power factor over 20000 A shall be 
—Trip out at 250%
—Dielectric at twice the rated test voltage
•100% 
| 
 | The circuit breaker is submitted to additional temperature tests performed as standard tests, except | 
| 
 | that the circuit breaker is installed in an enclosure. The dimensions and possible ventilations shall be | 
| 
 | recorded and shall be marked on the circuit breaker. | 
| Tests On | Shunt trip and Undervoltage  | 
| Accessories | endurance and dielectric tests. | 
| 
 | Overvoltage  | 
| 
 | without damage (this test does not apply to a shunt trip with an "a" contact connected in series). | 
| 
 | Operation: | 
| 
 | Shunt  | 
| 
 | fault protection shall operate at 55%). | 
| 
 | Undervoltage  | 
| 
 | circuit breaker between 35 and 70% of its rated voltage and shall  | 
| 
 | is at 85% or more of its rated voltage. | 
| 
 | |
| 
 | current" operations of the circuit breaker. | 
| 
 | Auxiliary and Alarm  | 
| 
 | overload, endurance and dielectric tests. | 
| 
 | Overload  | 
| 
 | voltage, with a  | 
| 
 | |
| 
 | factor in ac, and  | 
| 
 | auxiliary switches, and 10% of this number for alarm switches. | 
| 
 | Motor  | 
| 
 | for the circuit breaker endurance tests. The first 25 operations shall be conducted at 85% of the motor | 
| 
 | operator voltage rating. The circuit breaker is to be tripped during these tests. The next 25 operations | 
| 
 | shall be conducted at 110% of the motor operator voltage rating. The balance shall be completed at | 
| 
 | rated voltage without tripping the circuit breaker. | 
| ©  | 69 | 
