Compact® NSF and NSJ 150 to 600 A Circuit Breakers
Section
The
•Extract and/or rapidly replace the circuit breaker without having to touch connections
•Allow for addition of future circuits at a later date
Parts of a Plug-in Configuration
When the circuit breaker is in the connected position, the primary voltage is fed through the circuit breaker by means of multiple finger disconnects. Control voltage of internal accessories is provided through secondary disconnects.
Compact® circuit breaker (fixed mounted)
•Set of power and secondary disconnects that are added to the circuit breaker
•
•Safety trip, to be installed on the circuit breaker, which causes automatic tripping if the circuit breaker is ON before engaging or withdrawing it; the safety trip does not prevent circuit breaker operation, even when the circuit breaker is disconnected
•Mandatory short terminal shields
The
DRAWOUT MOUNTING
The chassis is made up of two side plates installed on the base and two other plates mounted on the circuit breaker.
06153079 | 06153080 |
Connected | Disconnected | Removed |
Chassis Functions All functions of the
•Disconnected position: the power circuits are disconnected, the circuit breaker is simply "withdrawn" and may still be operated (on, off,
•Circuit breaker may be locked using 1 to 3
•Auxiliaries can be tested using manual auxiliary connector
Mounting | • | On a backplate, through a front panel or on rails |
| • | Horizontally or vertically |