Compact® NSF and NSJ 150 to 600 A Circuit Breakers

Section 13—Supplementary Technical Information

Test Sequences

Sequence

Category of Devices

Tests

 

 

 

 

Trip Unit Control

 

 

 

Dielectric Properties

 

 

 

Mechanical and Electrical Endurance

1–General Characteristics

All Circuit Breakers

Overload

 

 

 

Dielectric Voltage Withstand

 

 

 

Temperature Rise

 

 

 

145%

Calibration (3 Phases Test)

 

 

 

 

 

 

 

 

Breaking Capacity During Operation (Ot-CO-t-CO)

2–Breaking Capacity During Operation

All Circuit Breakers

Dielectric Voltage Withstand

Temperature Rise

 

 

 

 

 

 

145%

Calibration (3 Phases Test)

 

 

 

 

 

 

 

 

 

200%

Calibration (Each Pole Separately)

3–Ultimate Breaking Capacity (Icu)

A

 

Ultimate Breaking Capacity (O-t-CO)

B if Icu > Icw

Dielectric Voltage Withstand

 

 

 

 

250%

Calibration (Each Pole Separately)

 

 

 

 

 

 

 

 

 

200%

Calibration (Each Pole Separately)

 

 

 

Short-time Current Withstand

4–Admissible Short Duration Current (Icw)

B

 

Temperature Rise

 

Breaking Capacity at Admissible Short-time Current (O-t-CO)

 

 

 

 

 

 

Dielectric Voltage Withstand

 

 

 

200%

Calibration (Each Pole Separately)

 

 

 

 

 

 

 

 

 

200%

Calibration (Each Pole Separately)

 

Icw = Ics Replaces Sequences 2

Short-time Current Withstand Icw

 

Breaking Capacity at Ics (O-CO-CO) at Maximum Relay Temp.

Combined Sequence

 

and 4

Icw = Ics = Icu Replaces

Dielectric Voltage Withstand

 

 

 

Sequences 2, 3 and 4

Temperature Rise

 

 

 

 

 

 

200%

Calibration (Each Pole Separately)

 

 

 

 

 

 

72

© 1995–2003 Schneider Electric All Rights Reserved

Page 72
Image 72
Schneider Electric Class 615 dimensions Test Sequences, Sequence Category of Devices Tests