Compact® NSF and NSJ 150 to 600 A Circuit Breakers
Section 
Test Sequences
| Sequence | Category of Devices | Tests | 
 | |||
| 
 | 
 | 
 | • | Trip Unit Control | ||
| 
 | 
 | 
 | • | Dielectric Properties | ||
| 
 | 
 | 
 | • | Mechanical and Electrical Endurance | ||
| All Circuit Breakers | • | Overload | ||||
| 
 | 
 | 
 | • | Dielectric Voltage Withstand | ||
| 
 | 
 | 
 | • | Temperature Rise | ||
| 
 | 
 | 
 | • | 145% | Calibration (3 Phases Test) | |
| 
 | 
 | 
 | 
 | 
 | ||
| 
 | 
 | 
 | • | Breaking Capacity During Operation  | ||
| All Circuit Breakers | • | Dielectric Voltage Withstand | ||||
| • | Temperature Rise | |||||
| 
 | 
 | 
 | ||||
| 
 | 
 | 
 | • | 145% | Calibration (3 Phases Test) | |
| 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 
 | 
 | • | 200% | Calibration (Each Pole Separately) | |
| A | 
 | • | Ultimate Breaking Capacity  | |||
| B if Icu > Icw | • | Dielectric Voltage Withstand | ||||
| 
 | ||||||
| 
 | 
 | 
 | • | 250% | Calibration (Each Pole Separately) | |
| 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 
 | 
 | • | 200% | Calibration (Each Pole Separately) | |
| 
 | 
 | 
 | • | |||
| B | 
 | • | Temperature Rise | |||
| 
 | • | Breaking Capacity at Admissible  | ||||
| 
 | 
 | 
 | ||||
| 
 | 
 | 
 | • | Dielectric Voltage Withstand | ||
| 
 | 
 | 
 | • | 200% | Calibration (Each Pole Separately) | |
| 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 
 | 
 | • | 200% | Calibration (Each Pole Separately) | |
| 
 | • | Icw = Ics Replaces Sequences 2 | • | |||
| 
 | • | Breaking Capacity at Ics  | ||||
| Combined Sequence | 
 | and 4 | ||||
| • | Icw = Ics = Icu Replaces | • | Dielectric Voltage Withstand | |||
| 
 | ||||||
| 
 | 
 | Sequences 2, 3 and 4 | • | Temperature Rise | ||
| 
 | 
 | 
 | ||||
| 
 | 
 | 
 | • | 200% | Calibration (Each Pole Separately) | |
| 
 | 
 | 
 | 
 | 
 | 
 | |
| 72 | ©  | 