Compact® NSF and NSJ 150 to 600 A Circuit Breakers
Section 13—Supplementary Technical Information
© 1995–2003 SchneiderElectric All Rights Reserved
72
Test Sequences
Sequence Category of Devices Tests
1–General Characteristics All Circuit Breakers
•Trip Unit Control
•Dielectric Properties
•Mechanical and Electrical Endurance
•Overload
•Dielectric Voltage Withstand
•Temperature Rise
•145% Calibration (3 Phases Test)
2–Breaking Capacity During Operation All Circuit Breakers
•Breaking Capacity During Operation (Ot-CO-t-CO)
•Dielectric Voltage Withstand
•Temperature Rise
•145% Calibration (3 Phases Test)
3–Ultimate Breaking Capacity (Icu) A
B if Icu > Icw
•200% Calibration (Each Pole Separately)
•Ultimate Breaking Capacity (O-t-CO)
•Dielectric Voltage Withstand
•250% Calibration (Each Pole Separately)
4–Admissible Short Duration Current (Icw) B
•200% Calibration (Each Pole Separately)
•Short-time Current Withstand
•Temperature Rise
•Breaking Capacity at Admissible Short-time Current (O-t-CO)
•Dielectric Voltage Withstand
•200% Calibration (Each Pole Separately)
Combined Sequence
•Icw = Ics Replaces Sequences 2
and 4
•Icw = Ics = Icu Replaces
Sequences 2, 3 and 4
•200% Calibration (Each Pole Separately)
•Short-time Current Withstand Icw
•Breaking Capacity at Ics (O-CO-CO) at Maximum Relay Temp.
•Dielectric Voltage Withstand
•Temperature Rise
•200% Calibration (Each Pole Separately)