Compur Statox 4120
Example of cable specifications: |
|
|
Max. cable capacity: | l x CL = Co - Ci | = 107 nF |
Max. cable inductivity: | l x LL = Lo - Li | = 6,6 mH |
Diameter: | > 0,75 mm2 |
|
The Statox 4120 Systems will work reliably if the electrical resistance is : RL < 50 Ω. Most commonly the maximum length is limited by the cable capacity.
Example: Cable diameter is 1,0 mm2 (0,04 in), CL = 90 pF/m, LL = 0.7mH/km, RL / km = 19,5 Ω. The maximum cable length results to be
l = Co − Ci = 1189 m (3900 ft), the electrical resistance is
90 pF / m
RL = 2 x 1.189km (0,738 miles) x 19,5 Ω/km = 46,4Ω. So RL < 50Ω is OK.
Sensor head connection procedure:
Open sensor head, remove cable gland.
Connect signal cable to terminals X3/1 und X3/2, polarity does not matter. (DIN EN
Fasten cable gland.
Connect battery pack: - Blue to terminal X4/1
-Orange to terminal X4/2
-Red to terminal X4/3
Connect signal cable to backplane of the rack. (See chapter 3.2)
pic.9: Sensor head pcb terminals
12