Compur Statox 4120

Control module:

Type:

Operating temperature: Storage temperature: Explosion protection : Operating environment: power:

Supply voltage:

Max. operating voltage Uo: Max. operating current Io: Max. external capacity Co: Max. external inductivity Lo: Display:

Analog output:

Relays:

Rack:

Type:

Explosion protection: Operating environment: Dimensions (HxBxT)

5331 0x0 (115 / 230 VAC) -20 to +40 oC

-30 to +60oC [EEx ib] IIC II 2 G

15 W per control module

115 / 230 VAC

22 V DC

50 mA DC

162nF

6.6mH

Bargraph

4-20 mA / 400 Ω max. 0-1 V / Ri = 1k Ω

24V 100 mA

5332 xxx (xxx: ½ 19” and 19” , 115 / 230 V AC) [EEx ib] IIC

II 2 G

½x 19“: 180x270x420 mm

19“: 180x485x420 mm

RFI : 180x485x505 mm

Diagnostic box:

Temperature range:

-20 to +40 oC

Weight:

0,9 kg

Dimensions (HxBxT)

50x190x160 mm

Explosion protection:

EEx ib IIC T6

Protection class:

IP30

Operation time:

max. 3 h

Charging time:

max. 14 h

31

Page 31
Image 31
Compur 4120 operation manual Control module, Rack, Diagnostic box