Control Console

Managing the Unit

Control Console

Options for using the Control Console

Access to the Control Console

The Control Console provides comprehensive management of the unit by one of the following modes of access:

Telnet, for remote management

A serial interface for local management

Only one user at a time may access the Environmental Monitoring Unitt. Serial interface users have precedence over Telnet users, and Telnet users have precedence over Web users.

Use a serial interface to access the Control Console:

1.Use the supplied configuration cable (APC part number 940- 0120) to connect the terminal port to one of the Probe Ports on the Environmental Monitoring Unit.

2.Set the terminal port for the following communication settings:

Baud Rate

2400

 

 

Data Bits

8

 

 

Stop Bits

1

 

 

Parity

None

 

 

Handshaking

None

 

 

Local Echo

Off

 

 

Terminal Type

ANSI (VT100)

 

 

3.To change the communications settings using HyperTerminal:

a.Make the needed changes.

b.Select Disconnect in the Call menu.

c.Select Connect in the Call menu.

d.Press ENTER

4.Log into the Control Console. (See Logging in on this page.)

Logging in

When prompted, enter the Administrator user name and password (apc,

 

by default, for both).

 

To change the user name, password, or timeout value, see User

 

Manager on page 16.

 

Continued on next page

Environmental Monitoring Unit: User’s Guide

4

Page 8
Image 8