Environmental Manager: Main Module 25
SensorsTemperature/Humidity (AP9335TH)Temperature accuracy ±2ºC (±3ºF), from 0 to 40ºC
(32 to 104ºF)
Humidity accuracy ±4% RH, 20 to 90% RH, at
25ºC (77ºF)
±8% RH, 30 to 80% RH,
from 15 to 30ºC (59 to 95ºF)
Sensor operating
temperature
–10 to 70ºC (14 to 159ºF)
User input
response time
200 mS
Maximum length of
cable
15.2 m (50 ft)
Temperature (AP9335T)Temperature accuracy ±2ºC (±3ºF), from 0 to 40ºC
(32 to 104ºF)
Sensor operating
temperature
–10 to 70ºC (14 to 159ºF)
Maximum length of
cable
15.2 m (50 ft)
A-LinkMaximum length of
cable
1000 m (3,280 ft)
BeaconMaximum length of
cable
100 m (330 ft)
Door contac tsMaximum length of
cable
100 m (330 ft)
Output VoltagesVoltages 12 Vdc, 24 Vdc
Current 75 mA total for 12 V and
24 V load
Relay OutputCurrent capacity of
relay outputs
1 A, 30 V AC/DC