Setup & Testing
Indoor Air Quality System SettingS Tables
The following tables contain the Indoor Air Quality system settings and their details.. Default settings are shown in bold.. Some settings are only present dependent upon the value of other settings..
The use of the included outdoor temperature sensor (recommended) enables additional Indoor Air Quality functionality.. If the outdoor temperature sensor was not enabled in the HVAC system settings, HVAC system setting 11, outdoor sensor, will be presented prior to entering the Indoor Air Quality system settings.
Please refer to the Model 8620 Owner’s Manual for further information about thermostat features.
Air Cleaning System Settings Table
|
| Factory default setting (bold) |
System setting | Description | and setting range |
Air Cleaner Installed | Selects if an air cleaner is installed. (If set to no, no other | No |
| air cleaning settings will be available..) | Yes |
Change Air Filter Reminder | The period for displaying the “Change Air Filter” message. | Off |
|
| 1 to 12 months or “Off” to disable |
Humidifier System Settings Table
Note: A humidifier can only be installed if ventilation is not installed and dehumidifier control is not set to whole home..
|
| Factory default setting (bold) |
System setting | Description | and setting range |
|
|
|
Humidifier Installed | Selects if a humidifier is installed. (If set to no, no other | No |
| humidifier settings will be available..) | Yes |
Humidifier Mode | Selects auto or manual mode.. Auto mode controls humidity | Auto |
| based on the humidity setting and outdoor temperature.. | Manual |
| Manual mode controls humidity based on the %RH setpoint. |
|
| (Auto mode is only available if outdoor sensor is set to yes..) |
|
Humidity Setpoint | Select the minimum difference between the humidifier | 10 Percent RH |
Deadband | and dehumidifier setpoints.. (Only available if humidifier | 10 to 20 Percent RH |
| mode is set to manual and dehumidifier control is set to air |
|
| conditioner.. Available in both |
|
Humidifier Operation | Selects when humidification is allowed to occur relative to | Heat Only |
| heating and fan operation.. | Heat or Fan |
|
| Forces Fan |
Change Water Panel | Selects the when the “Change Water Panel” message is | Off |
Reminder | displayed.. | 1 Per Season |
|
| 2 Per Season |
|
| 300 Hours |
|
| 600 Hours |
Reminder Month (Change | Change Water Panel Reminder set to 1 per Season: | October |
Water Panel Reminder set | Determines the month the “Change Water Panel” message | November |
to 1 per Season) | is displayed.. | December |
|
| January |
First Reminder Month | Change Water Panel Reminder set to 2 per Season: | February |
(Change Water Panel | Determines the first month the “Change Water Panel” | March |
Reminder set to 2 per | message is displayed.. | April |
Season) |
| May |
|
| June |
|
| July |
|
| August |
|
| September |
Second Reminder Start | Determines the second month the “Change Water Panel” | October |
Month | message is displayed.. (Only available when Change Water | November |
| Panel Reminder set to 2 per Season..) | December |
|
| January |
|
| February |
|
| March |
|
| April |
|
| May |
|
| June |
|
| July |
|
| August |
|
| September |
10
Setup & Testing
Dehumidifier System Settings Table
Note: Dehumidifier control can only be set to whole home if ventilation and humidification are not installed..
|
| Factory default setting (bold) |
System setting | Description | and setting range |
Dehumidifier Control | Selects method of dehumidification.(If set to none, no | None (no dehumidification installed) |
| other dehumidifier settings will be available..) | Whole Home |
|
| Air Conditioner |
Humidity Setpoint Deadband | Select the minimum difference between the humidifier | 10 Percent RH |
| and dehumidifier setpoints.. (Only available if | 10 to 20 Percent RH |
| humidifier mode is set to manual and dehumidifier |
|
| control is set to air conditioner.. Available in both |
|
|
| |
Lockout Dehumidifier During | Selects if dehumidification is disabled during a cooling | No |
Cooling | call.. (Only available if dehumidifier control is set to | Yes |
| whole home..) |
|
Dehumidifier Forces Fan | Select if dehumidification can turn on the fan.. (Only | No |
| available if dehumidifier control is set to whole home..) | Yes |
Dehumidifier Service | The period for displaying the “Dehum Service | Off |
Reminder | Reminder” message. (Only available if dehumidifier | 1 to 12 months or “Off” to disable |
| control is set to whole home..) |
|
Dehumidifier Overcooling | Selects the amount of overcooling that can occur | 3°F (1.5°C) |
Limit | for dehumidification.. (Only available if dehumidifier | 1°F to 3°F (0.5°C to 1.5°C) |
| control is set to air conditioner..) |
|
Dehumidify in Vacation | Selects if dehumidification with the air conditioner is | No |
Mode | done in Vacation Mode. (Only available if dehumidifier | Yes |
| control is set to air conditioner.. |
|
Vacation Dehumidifier Low | Sets the lowest temperature the air conditioner will cool | 75°F (24°C) |
Temp Limit | to meet RH setpoint in Vacation Mode. (Only available if | 70°F to 85°F (21°C to 29°C) |
| dehumidifier control is set to air conditioner..) |
|
Ventilation System Settings Table
Note: Ventilation can only be installed if humidification is not installed and dehumidifier control is not set to whole home..
|
| Factory default setting (bold) |
System setting | Description | and setting range |
Fresh Air Vent Installed | Selects if ventilation is installed.. | No |
| (If set to no, no other ventilation settings will be available.) | Yes |
Fresh Air Forces Fan | Selects if ventilation forces the fan on.. | No |
|
| Yes |
Fresh Air Setup | Selects if ventilation is configured through the ASHRAE setup | Timed |
| or Timed. If ASHRAE setup is selected, the hourly ventilation | ASHRAE |
| time will be calculated using the ASHRAE recommendations.. |
|
| If Timed |
|
| determined based on the Fresh Air Time value. |
|
Fresh Air Time | Selects how many minutes per hour that ventilation will be | 30 MIN/HR |
| active.. (Only available if fresh air setup is set to timed..) | 0 to 60 MIN/HR |
High Limit Outdoor | Selects if ventilation is disabled if the outdoor temperature | No |
Temp | exceeds the outdoor high limit. (Only available if fresh air setup | Yes |
| is set to timed and an outdoor temperature sensor is installed..) |
|
Outdoor High Limit | Sets the high temperature limit for ventilation.. (Only available if | 100°F (38°C) |
| high limit outdoor temp set to yes..) | 90°F to 100°F (32°C to 38°C) |
Low Limit Outdoor Temp | Selects if ventilation is disabled if the outdoor temperature | No |
| exceeds the outdoor low limit. (Only available if fresh air setup | Yes |
| is set to timed and an outdoor temperature sensor is installed..) |
|
Outdoor Low Limit | Sets the low temperature limit for ventilation.. (Only available if | 10°F |
| low limit outdoor temp set to yes..) | |
High Limit Indoor RH | Selects if ventilation is disabled if the indoor RH exceeds the | No |
| indoor RH limit.. (Only available if fresh air setup is set to timed..) | Yes |
Indoor RH Limit | Sets the high indoor RH limit for ventilation.. (Only available if | 60% |
| high limit indoor RH is set to yes..) | 50% to 70% |
11