Installation
Installation
Installation location recommendations
Thermostat should be mounted:
• On an interior wall, in a frequently occupied space. |
• Approximately 5‘ above floor. |
• At least 18” from outside wall. |
Do not mount thermostat:
• Behind doors, in corners or other dead air spaces. |
• In direct sunlight, near lighting fixtures, or other |
appliances that give off heat.. |
Remote temperature sensor (optional)
A remote temperature sensor can be used if the thermostat has to be mounted in a concealed location.. A 8051 flush mount or 8053 surface mount remote temperature sensor can be attached to the T1 and T2 terminals and mounted in a recommended area.. The remote sensor must be enabled in the installer setup menu.. When the remote sensor is installed it overrides the internal sensor..
• Thermostat can be mounted to a vertical junction box. |
Outdoor temperature sensor (INCLUDED)
• On an outside or unconditioned area wall. |
• In the flow of a supply register, in stairwells, or near |
outside doors.. |
• On a wall with concealed pipes or ductwork. |
Remote temperature sensor should be mounted:
•On an interior wall, in a frequently occupied space.
•Approximately 5‘ above floor.
•At least 18” from outside wall.
•Using less than 300’ of wire.
Do not mount remote sensor:
• Behind doors, in corners or other dead air spaces. |
• In direct sunlight, near lighting fixtures, or other |
appliances that give off heat.. |
• On an outside or unconditioned area wall. |
• In the flow of a supply register, in stairwells, or near |
outside doors.. |
Outdoor temperature can be measured by attaching the included 8052 sensor to the S1 and S2 terminals.. The outdoor sensor must be enabled in the installer setup menu..
Heat pump models can use the outdoor temperature to effectively utilize the heat pump:
•When the outdoor temperature is less than the Low Balance Point, the heat pump will be locked out and only auxiliary heating will be used.
•When the outdoor temperature is higher than the High Balance Point, the auxiliary heating will be locked out and only the heat pump will be used to provide heating..
Indoor Air Quality functions can use the outdoor temperature sensor to:
•Control humidification setpoint based on outdoor temperature to prevent condensation
•Lock out humidification for temperatures over 60°F or below
•Lock out ventilation based on high and/or low outdoor temperatures.
•Display outdoor temperature on thermostat.
Outdoor temperature sensor should be mounted:
•On side of building out of direct sunlight (north side recommended).
•Above snow line.
•At least 3’ away from exhaust vents and condensing lines.
•Using less than 300’ of wire.
•Do not route wires along 120 VAC lines.
I2 | C | I1 O/B Y Y2 G RC R W2 W | L S2 S1 T1 T2 |
• On a wall with concealed pipes or ductwork. |
• Near 120 VAC lines. |
I2 | C | I1 O/B Y Y2 G RC R W2 W | L S2 S1 T1 T2 |
Thermostat mounting
1..Remove the rear mounting plate from the thermostat..
2..Pull wires through the opening on the back of the thermostat..
3..Position and level the mounting plate of the thermostat on wall and mark the hole locations with a pencil..
4.Drill 1/4” holes and insert supplied anchors
(drywall only)..
5.Place mounting plate over anchors, insert and tighten screws..
6..Seal wire entry holes to prevent drafts affecting temperature readings..
2 | 3 |