Ariston A/27 MFFI, A/23 MFFI, 47-116-12, 47-116-10 installation instructions Coaxial System

Models: A/27 MFFI 47-116-10 47-116-12 A/23 MFFI

1 28
Download 28 pages 59.87 Kb
Page 13
Image 13

 

Exhaust Type

Maximum Extension Diameter of Pipes

Use of a Restrictor

Risk of Condensation Forming

 

Exhaust/Air

(mm)

on the Discharge Side

 

 

 

 

 

 

 

 

 

 

C12 (xx)

4 m

ø 60 /100

L* < 0.5 m

 

Coaxial

 

 

 

 

 

System

C32 (xx)

4 m

ø 60 /100

L* < 0.5 m

 

 

C42 (xx)

4 m

ø 60 /100

L* < 0.5 m

 

 

 

23 kW

27 kW

 

 

 

 

 

 

 

 

 

 

 

C12 (xy)

54 m

46 m

ø 80

L < 7 m (23 kW) L < 5 m (27 kW)

L > 4 9 m (23 kW) L > 6.5 m (27 kW)

 

C32 (xy)

54 m

46 m

ø 80

L < 7 m (23 kW) L < 5 m (27 kW)

L > 4.9 m (23 kW) L > 6.5m (27 kW)

Twin Pipe

 

 

 

 

 

 

Systems

C42 (xy)

54 m

46 m

ø 80

L < 7 m (23 kW) L < 5 m (27 kW)

L > 4.9m (23 kW) L > 6.5m (27 kW)

 

C52 (xy)

17 m

17 m

ø 80

L < 7 m (23 kW) L < 5 m (27 kW)

L > 4.9m (23 kW) L > 5.3m (27 kW)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(*) L = Length of Piping

In calculating the lengths of the pipes, the maximum length must also take into consideration the values for the exhaust/air intake end terminals, as well as 90° elbows for coaxial systems.

The C52 types must comply with the following requirements:

1.The discharge/intake vent pipes must have the same diameter of ø 80 mm.

2.The maximum combined flue length is 17 m. In this case the minimum length for the air intake pipe is 1 meter; the maximum length of ver tical exhaust pipe must be a maximum of 12 m.

3.If an elbow is inserted into the discharge/ventilation system, the calculation of the overall extension must take into consideration the values for each curve, as indicated in the table.

4.The exhaust pipe must extend at least 0.5 m above the ridge of the roof if it is located on a side other than that for the air intake (this is not obligatory if the exhaust and air intake pipes are located on the same side of the building).