15
Drain Frequency 6
Default: 12 hours 12 (Default)
24
48
96
No Drain
Real Time
Real Time Set
24 Hour Clock
Drain Time
1
5 (Default)
10
Load Default
Reset all to Default? Confirm Cancel
Signal Type
0-10 Vdc (Default)
0-5VDC
1.9V - 3.9V
4-20mA
Sensor Select
Humidistat (Default)
RH Sensor
High Limit Sensor
High Limit Set Point 85% (Default)
Outside Temperature
High Limit Set 1°C / Low Limit Set 1°C
Lowest RH Set Point 15% (Default)
PID Settings PB Proportion Brand 0-900
PID PB 10; PID IRV 10 IRV Integral Reset Value 0-500
PIDF DG 200; PID SI 10 DG Derivative Gain 0-500
SI Interval 0-30
Records
Error List 01 05-04-01 16:00 (example)
See Page 25 for list of possible errors. Fill time out to low level
Display the RH graph RH graph of the last 30 days
This menu can be shown when RH sensor is selected
Set Date and Time
YYYY-MM-DD; Time (24 Hr. Format) Date and Time from realtime IC
Save Settings SAVE SETTINGS
Confirm Cancel
Must be done after any 'Operation Setup' menu changes.
Operation Setup - Continued
Operation Setup - Continued