Table 48-1. LonWorks Variable List
49
Map Descriptor Name
Data Array
Name
Data Array
Offset
Lon Function Function
Node
Name
SNVT Type
SNVT
option
oFILLSTATUS BITA 0 NVPO Server Lon_1 SNVT_switch state
oDRAINSTATUS BITA 1 NVPO Server Lon_1 SNVT_switch state
oCON1 BITA 2 NVPO Server Lon_1 SNVT_switch state
oCON2 BITA 3 NVPO Server Lon_1 SNVT_switch state
oCON3 BITA 4 NVPO Server Lon_1 SNVT_switch state
oCON4 BITA 5 NVPO Server Lon_1 SNVT_switch state
oCOMTYPE BITB 0 NVPO Server Lon_1 SNVT_switch state
oRH_SELECT BITB 1 NVPO Server Lon_1 SNVT_switch state
oHL_SELECT BITB 2 NVPO Server Lon_1 SNVT_switch state
oOUTTEM_SELECT BITB 3 NVPO Server Lon_1 SNVT_switch state
oNETWORK_ENABLE BITB 4 NVPO Server Lon_1 SNVT_switch state
oMOD_FILL_ENABLE BITB 5 NVPO Server Lon_1 SNVT_switch state
oRH_REQUIRE SINTA 0 NVPO Server Lon_1 SNVT_lev_percent -
oOUTPUT SINTA 1 NVPO Server Lon_1 SNVT_count_f -
oWATER_LEVEL SINTA 2 NVPO Server Lon_1 SNVT_count_f -
oRUN_STATUS SINTA 3 NVPO Server Lon_1 SNVT_count_f -
oBEDLIFE_H SINTA 4 NVPO Server Lon_1 SNVT_count_f -
oBEDLIFE_M SINTA 5 NVPO Server Lon_1 SNVT_count_f -
oRUNTIME_H SINTA 6 NVPO Server Lon_1 SNVT_count_f -
oRUNTIME_M SINTA 7 NVPO Server Lon_1 SNVT_count_f -
oDRAINTIME_H SINTA 8 NVPO Server Lon_1 SNVT_count_f -
oDRAINTIME_M SINTA 9 NVPO Server Lon_1 SNVT_count_f -
oIDLETIME_H SINTA 10 NVPO Server Lon_1 SNVT_count_f -
oIDLETIME_M SINTA 11 NVPO Server Lon_1 SNVT_count_f -
oRH_VALUE SINTA 12 NVPO Server Lon_1 SNVT_lev_percent -
oDUCT_VALUE SINTA 13 NVPO Server Lon_1 SNVT_lev_percent -
oOUTSIDE_TEMP SINTA 14 NVPO Server Lon_1 SNVT_temp_p -
oWATER_TEMP SINTA 15 NVPO Server Lon_1 SNVT_temp_p -
oHEAT_TEMP SINTA 16 NVPO Server Lon_1 SNVT_temp_p -
oFAULT SINTA 17 NVPO Server Lon_1 SNVT_count_f -
oCON_NUMBER SINTA 18 NVPO Server Lon_1 SNVT_count_f -
oHEAT_POWER SINTA 19 NVPO Server Lon_1 SNVT_count_f -
oLANGUAGE SINTB 0 NVPO Server Lon_1 SNVT_count_f -
oRH_SET SINTB 1 NVPO Server Lon_1 SNVT_lev_percent -
oHL_POINT SINTB 2 NVPO Server Lon_1 SNVT_lev_percent -
oOUTTEMP_H SINTB 3 NVPO Server Lon_1 SNVT_temp_p -
oOUTTEMP_L SINTB 4 NVPO Server Lon_1 SNVT_temp_p -
oOUTRH_L SINTB 5 NVPO Server Lon_1 SNVT_lev_percent -
oRUN_MODE SINTB 6 NVPO Server Lon_1 SNVT_count_f -
oWATER_TEMP_SET SINTB 7 NVPO Server Lon_1 SNVT_temp_p -
oBED_LIFE SINTB 8 NVPO Server Lon_1 SNVT_count_f -
oDRAIN_FREQ SINTB 9 NVPO Server Lon_1 SNVT_count_f -
oDRAIN_TIME SINTB 10 NVPO Server Lon_1 SNVT_count_f -
oSENSER_TYPE SINTB 11 NVPO Server Lon_1 SNVT_count_f -
oPID_DIV SINTB 12 NVPO Server Lon_1 SNVT_count_f -
oPID_PB SINTB 13 NVPO Server Lon_1 SNVT_count_f -
oPID_SI SINTB 14 NVPO Server Lon_1 SNVT_count_f -
oPID_DG SINTB 15 NVPO Server Lon_1 SNVT_count_f -
oMOD_FILL_FREQ SINTB 16 NVPO Server Lon_1 SNVT_count_f -
oMOD_FILL_TIME SINTB 17 NVPO Server Lon_1 SNVT_count_f -
oWATER_TEMP_COMP SINTB 18 NVPO Server Lon_1 SNVT_temp_p -
oHEAT_TEMP_COMP SINTB 19 NVPO Server Lon_1 SNVT_temp_p -
iCOMTYPE BITB_in 0 NVUI Server Lon_1 SNVT_switch state
iRH_SELECT BITB_in 1 NVUI Server Lon_1 SNVT_switch state
iHL_SELECT BITB_in 2 NVUI Server Lon_1 SNVT_switch state
iOUTTEM_SELECT BITB_in 3 NVUI Server Lon_1 SNVT_switch state
iNETWORK_ENABLE BITB_in 4 NVUI Server Lon_1 SNVT_switch state
iMOD_FILL_ENABLE BITB_in 5 NVUI Server Lon_1 SNVT_switch state
iLANGUAGE SINTB_in 0 NVUI Server Lon_1 SNVT_count_f -
iRH_SET SINTB_in 1 NVUI Server Lon_1 SNVT_lev_percent -
iHL_POINT SINTB_in 2 NVUI Server Lon_1 SNVT_lev_percent -
iOUTTEMP_H SINTB_in 3 NVUI Server Lon_1 SNVT_temp_p -
iOUTTEMP_L SINTB_in 4 NVUI Server Lon_1 SNVT_temp_p -
iOUTRH_L SINTB_in 5 NVUI Server Lon_1 SNVT_lev_percent -
iRUN_MODE SINTB_in 6 NVUI Server Lon_1 SNVT_count_f -
iWATER_TEMP_SET SINTB_in 7 NVUI Server Lon_1 SNVT_temp_p -
iBED_LIFE SINTB_in 8 NVUI Server Lon_1 SNVT_count_f -
iDRAIN_FREQ SINTB_in 9 NVUI Server Lon_1 SNVT_count_f -
iDRAIN_TIME SINTB_in 10 NVUI Server Lon_1 SNVT_count_f -
iSENSER_TYPE SINTB_in 11 NVUI Server Lon_1 SNVT_count_f -
iPID_DIV SINTB_in 12 NVUI Server Lon_1 SNVT_count_f -
iPID_PB SINTB_in 13 NVUI Server Lon_1 SNVT_count_f -
iPID_SI SINTB_in 14 NVUI Server Lon_1 SNVT_count_f -
iPID_DG SINTB_in 15 NVUI Server Lon_1 SNVT_count_f -
iMOD_FILL_FREQ SINTB_in 16 NVUI Server Lon_1 SNVT_count_f -
iMOD_FILL_TIME SINTB_in 17 NVUI Server Lon_1 SNVT_count_f -
iWATER_TEMP_COMP SINTB_in 18 NVUI Server Lon_1 SNVT_temp_p -
iHEAT_TEMP_COMP SINTB_in 19 NVUI Server Lon_1 SNVT_temp_p -