Table 47-1. BACnet Variable List
48
BACnet Data Type
Data
Address
Description Attribute
1 Fill valve status 0:off 1:on
2 Drain valve status 0:off 1:on
3 contactor 1 status 0:off 1:on
4 contactor 2 status 0:off 1:on
5 contactor 3 status 0:off 1:on
6 contactor 4 status 0:off 1:on
8 Network control 0:Local 1:Remote
1 comm type 0:485 1:PSP
2 Sensor select 0:Humidistat 1:RH sensor
3 High limit sensor select 0:not use 1:use
4 Outside temperature 0:not use 1:use
5 Network enable 0:disable 1:enable
6 Modulating Fill enable 0:enable 1:disable
1 Desired RH
2 Output
3 Water level 0:low 1:normal 2:high 3:exception
4 Run status 0:Idle 1:Gen 10:frequent Draining 4:bed drying 5:Failure 6:Drain 7:heat 9:Fill
5Bed life (Hours)
6Bed life (Minutes)
7Run Time (Hours)
8Run Time (Minutes)
9Drain Freq (Hours)
10 Drain Freq (Minutes)
11 Idle Time (Hours)
12 Idle Time (Minutes)
13 RH value
14 Duct value
15 Outside temperature
16 Water temperature
17 Heat temperature
18
Failure 1:Over temperature 2:High humidity/sail switch circuit is open 3:Illegal level switch state 4:Unit
have reached 100% of bed life 5:Fill time out to low level 6:Water level dropped below level during
normal run 7:Fill time out from low to high level 8:Water level above high level time out 9:Water level has
not dropped below low level during an emptydrain 10:End of bed dring
19 Contactor number
20 Contactor Power 0:1000W 1:3000 2:5000W 3:6650W 4:8000W
1 Language Select
2 Set RH(Set Desired RH) or Desired % Output
3 High set point
4 Outside temperature high set point
5 Outside temperature low set point
6 Outside RH low set point
7 Run mode 1:Steam Gen 2:Manual Fill 3:Manual Drain 4:Unit stop
8 AQUASTAT
9
Bed life 0:500Hours 1:750Hours 2:1000Hours 3:1250Hours 4:1500Hours 5:1750Hours 6:2000Hours
7:2250Hours 8:2500Hours 9:3000Hours 10:No bed
10
Drain Freq 0:6Hours 1:12Hours 2:24Hours 3:48Hours 4:96Hours
11 Drain time 0:1Minutes 1:5Minutes 2:10Minutes
12 Signal type 0:0-10V 1:0-5V 2:1.9-3.9V 3:4-20mA
13 PID_DIV
14 PID_PB
15 PID_SI
16 PID_DG
17 Modulating Fill Freq
18 Modulating Fill time
19 Water temperature compensate
20 Heat temperature compensate
Binary Input
Binary Output
Analog Input
Analog Output
Read Only
Read / Write
Read Only
Read / Write