Armstrong World Industries EHU-704 Duct Mounted Control Humidistat, High Limit Duct Humidistat

Models: EHU-701 EHU-700 Series EHU-704 EHU-703

1 40
Download 40 pages 20.75 Kb
Page 11
Image 11
1.9 - 3.9 Vdc

Figure 11-1

1.9 - 3.9 Vdc

Voltage Source

17

Black

Part No.

White

C1471

Ground

2

Green

Stat In

1

or

 

N/C

20

 

C1472

Set BJ4 Stat Input Selector to 1.9 - 3.9 Vdc

Set BJ5 Voltage Source to 12 Vac

 

 

On-Off Humidistat

Switch Opens on RH Rise

Voltage Source

17

 

Brown

Part No.

 

 

A8581

Ground

2

 

Orange

Stat In

1

 

or

 

 

N/C

20

 

 

A8581A

Set BJ4 Stat Input Selector to On/Off Set BJ5 Voltage Source to +5 Vdc

4-20 mA & 0-10 Vdc Setting*

Voltage Source

17

-

Ground

2

+

Stat In

1

 

N/C

20

 

Set BJ4 Stat Input Selector to 0-10 Vdc or 4-20 mA

0-135 Ω Ohm Potentiometer

 

 

 

Part No.

Voltage Source

17

 

A6707A

Ground

2

 

or

Stat In

1

 

A18611

 

N/C

20

 

Humidity

 

 

 

Increase

Set BJ4 Stat Input Selector to 0-135 Ohm

Set BJ5 Voltage Source to +5 Vdc

*See Figure 10-1 for Armstrong 0-10 Vdc Humidistat Connections

Duct Mounted Control Humidistat:

Duct-mounted control humidistats are also available for installation where sensing and control of return air or exhaust air ducts is preferable. (Figure 10-1)

Please refer to manufacturer's recommendations for further information on the location, mounting, and operation of the various control humidistats.

10)HIGH LIMIT DUCT HUMIDISTAT

Remove the jumpers tab from terminals 10 & 14 and wire the high limit stat between these terminals. Refer to Figure 10-1 and Figure 11-1 (the overall wiring diagram) for more information. A duct mounted high limit humidistat is recommended to prevent over-saturation of the duct air. Use an on-off controller that opens on fault (high humidity). Humidistat should be set for a maximum of 90% RH. Alternately, a modulation high limit humidistat may be used on applications such as variable air volume (VAV). Locate the high limit humidistat approximately 10' (3m) downstream of the dispersion manifold. If 10' (3m) is not available, consult the factory.

11)AIRFLOW SWITCH

An airflow switch is recommended to deactivate the humidifier when there is insufficient air flow in a duct system. A duct pressure switch is preferred as an airflow sensor. The pressure switch should open on insufficient airflow (opens on fault). Airflow switch should be mounted in supply air duct upstream of humidifier dispersion. Remove the jumper tabs between terminals 9 & 15 and wire the airflow sensor between these terminals. See Figure 11-1 and Figure 12-1 (the overall wiring diagram) for more information. Complete installation and wiring instructions are contained in the duct pressure switch package.

NOTE: LIMIT SWITCHES (HIGH LIMIT AND AIRFLOW SWITCHES) OPEN ON FAULT.

11

Page 11
Image 11
Armstrong World Industries EHU-704, EHU-703 Duct Mounted Control Humidistat, High Limit Duct Humidistat, Airflow Switch