Figure
1.9 - 3.9 Vdc
Voltage Source | 17 | Black | Part No. | |
White | C1471 | |||
Ground | 2 | |||
Green | ||||
Stat In | 1 | or | ||
| ||||
N/C | 20 |
| C1472 |
Set BJ4 Stat Input Selector to 1.9 - 3.9 Vdc
Set BJ5 Voltage Source to 12 Vac
|
|
| ||
Switch Opens on RH Rise | ||||
Voltage Source | 17 |
| Brown | Part No. |
|
| A8581 | ||
Ground | 2 |
| Orange | |
Stat In | 1 |
| or | |
|
| |||
N/C | 20 |
|
| A8581A |
Set BJ4 Stat Input Selector to On/Off Set BJ5 Voltage Source to +5 Vdc
4-20 mA & 0-10 Vdc Setting*
Voltage Source | 17 | - | |
Ground | 2 | ||
+ | |||
Stat In | 1 | ||
| |||
N/C | 20 |
|
Set BJ4 Stat Input Selector to
0-135 Ω Ohm Potentiometer
|
|
| Part No. |
Voltage Source | 17 |
| A6707A |
Ground | 2 |
| or |
Stat In | 1 |
| A18611 |
| |||
N/C | 20 |
| Humidity |
|
|
| Increase |
Set BJ4 Stat Input Selector to
Set BJ5 Voltage Source to +5 Vdc
*See Figure
Duct Mounted Control Humidistat:
Please refer to manufacturer's recommendations for further information on the location, mounting, and operation of the various control humidistats.
10)HIGH LIMIT DUCT HUMIDISTAT
Remove the jumpers tab from terminals 10 & 14 and wire the high limit stat between these terminals. Refer to Figure
11)AIRFLOW SWITCH
An airflow switch is recommended to deactivate the humidifier when there is insufficient air flow in a duct system. A duct pressure switch is preferred as an airflow sensor. The pressure switch should open on insufficient airflow (opens on fault). Airflow switch should be mounted in supply air duct upstream of humidifier dispersion. Remove the jumper tabs between terminals 9 & 15 and wire the airflow sensor between these terminals. See Figure
NOTE: LIMIT SWITCHES (HIGH LIMIT AND AIRFLOW SWITCHES) OPEN ON FAULT.