PRE-INSTALLATION

PRE-INSTALLATION

1)CHECK SHIPMENT

A claim should be filed with the transportation company (and reported to Armstrong) if any items are missing or damaged. Your shipment will arrive in two or three cartons.

One carton holds the humidifier with the steam generator installed, the control humidistat and sensing element, two short steam hoses, hose clamps, mounting plate and lag screws, and a clear drain hose. If you have ordered a duct pressure switch or a high limit stat, these too will be in the humidifier carton.

The steam dispersion tube(s) and fittings are contained in another carton ( two for the EHU 704).

 

Two complete sets of

Figure 4-1. EHU-701

 

 

installation instructions have

 

 

 

been shipped with your unit.

 

 

 

One is for the installer's use.

 

 

 

The second is for the owner's

 

 

 

files.

 

4" Side

 

 

 

Clearance

2)

CHECK LOCAL CODES

 

Both Sides

 

Series EHU-700 humidifiers

 

 

 

should be installed in

 

 

 

accordance with ALL

 

 

 

applicable building, plumbing,

 

 

 

and electrical codes.

24" Min. Steam

 

 

 

 

3)

SITE SELECTION

Generator

5" Min. Drain

Tank Removal

Connection Access

Electronic steam humidifiers

 

 

must be installed in locations

 

 

that allow routine inspection

 

 

and accessibility for maintenance

Figure 4-2. EHU-703/704

 

operations. See Figures 4-1 & 4-2

 

 

 

for access space.

 

 

Do not place electronic steam humidifers

4" Side

24" Side

Clearance

Clearance

in locations where unusual instances of

 

 

malfunction of the humidifier or the

 

 

system might cause damage to

 

 

non-repairable or un-replaceable,

24" Front

 

or priceless property.

Clearance

 

 

 

5" Min. Drain

 

 

Connection Access

4

Page 4
Image 4
Armstrong World Industries EHU-700 Series, EHU-703 Pre-Installation, Check Shipment, Check Local Codes, Site Selection