Chapter 1. Introduction

 

 

 

 

 

 

 

 

 

No.

Item

Description

 

 

 

1

Power Outlets*

Total : 6 x IEC320 C13 + 10 x IEC320 C19

 

 

Bank 1: Outlet 1–8; 3 x C13 + 5 x C19

 

 

Bank 2: Outlet 9–16; 3 x C13 + 5 x C19

 

 

 

2

Port and LED Panel

The Port and LED panel contains:

 

 

Š Readout Section and LEDs

 

 

Š Environmental Sensor Ports

 

 

Š LAN Port

 

 

Š Door Sensor Port

 

 

Š Reset Switch

 

 

Full details of this section are provided on

 

 

page 23.

 

 

 

3

Circuit Breakers

As a safety measure, if there is an overcurrent

 

 

situation regarding the device’s power, the circuit

 

 

breakers will trip. Press the button to recover

 

 

normal operation.

 

 

Warning: See Resetting the Circuit Breaker,

 

 

page 79 for important information about resetting a

 

 

tripped circuit breaker.

 

 

 

4

Power Cord

Plug the cord into an AC power source.

 

 

Š B models connect to a NEMA L6-30P source

 

 

Š G models connect to an IEC 60309 32A source

 

 

 

5

Outlet Status LEDs

These 16 LEDs indicate outlet status.

 

 

Lights ORANGE for powered on.

 

 

Off for powered off.

 

 

 

Note: Holes for ATEN Lok-U-Plug cable holders are located around the outlets. See Securing the Cables, page 35, for further information.