Baldor MN2410 manual Appendix D Premier OHV100E Series, Figure D-1 OHV100E Operator Panel

Models: MN2410

1 60
Download 60 pages 30.4 Kb
Page 47
Image 47

Appendix D

Premier OHV100E Series

Information in this Appendix applies to the OHV100E Baldor Generator.

Caution: The brass connecting tab on some 120VAC duplex receptacles have been removed. Each receptacle is powered by a separate generator winding. When replacing a receptacle, inspect the brass tab that normally links both receptacles. If it is removed, be sure to remove the brass tab from the replacement receptacle before it is installed. Failure to remove the tab will cause a direct short to the generator windings and cause possible generator damage.

Operator Panel Configuration

Figure D-1 OHV100E Operator Panel

AUTO IDLER

NEMA

L5-30R

 

Auto Idler Switch.

ON - Auto idler is active, engine RPM will reduce when load is removed.

ON

ELAPSED

TIME

AC

VOLTMETER

AC CIRCUIT

BREAKERS

OFF

30 AMPS

 

120 VOLTS

120 VOLTS

 

50 AMPS

120/240 VOLTS

NEMA

L14-30R

30 AMPS

120 VOLTS

120/240 VOLTS

 

OFF - Engine runs at fixed speed (set by governor).

Elapsed Time.

Displays the total run time hours of the generator set.

AC Voltmeter.

This voltmeter displays the voltage level being produced by the generator set.

AC Circuit Breakers.

Provide overload protection for the generator set.

120 Volts NEMA 5-20R GFCI Receptacle.

This ground fault circuit interrupter duplex receptacle is rated at 125VAC, 20 Amps.

30 AMPS 120 Volts NEMA L5-30R Receptacle. Twist-lock style receptacle rated for 125VAC, 30 Amps.

30 AMPS 120/240 Volts NEMA L14-30R Receptacle. Twist-lock style receptacle rated for 125/250VAC, 30 Amps.

50 AMPS 120/240 Volts CS6369 Receptacle.

Twist-lock style receptacle rated for 125/250VAC, 50 Amps.

MN2410

Premier OHV100E Series D-1