Baldor Series PC Mutlifuel manual Nut Washer Ground Wire Lug Washer Stud Frame Earth Ground

Models: Series PC Mutlifuel

1 34
Download 34 pages 51.12 Kb
Page 15
Image 15
Nut

Electrical Connections Continued

Table 3-1 Single Phase Power Receptacle Description

Model

Electrical Connection Information (Receptacle Provided at Panel)

 

 

 

 

 

 

Straight 120VAC

Twist Lock 120VAC

Twist Lock 120/240VAC

Rated Watts/

 

(20Amp)

(30Amp)

(30Amp)

(Full load Amps

 

 

 

 

120/240)

 

 

 

 

 

PC30H

3- 15AMP 120VAC

 

 

3000 / (22.5/-)

PC40H

2- 5-20R GFCI 120VAC

1- L5-30R 120VAC

1- L14-30R 120/240VAC

4000 / (33.3/16.7)

PC50H

2- 5-20R GFCI 120VAC

1- L5-30R 120VAC

1- L14-30R 120/240VAC

5000 / (33.3/16.7)

PC60H

2- 5-20R GFCI 120VAC

1- L5-30R 120VAC

1- L14-30R 120/240VAC

6000 / (45.8/22.9)

PC90VE

2- 5-20R GFCI 120VAC

1- L5-30R 120VAC

1- L14-30R 120/240VAC

9000 / (66.7/33.4)

Note: GFCI is Ground Fault Protected power.

Class 1 wiring methods must be used for field wiring connections to terminals of a Class 2 circuit.

Figure 3-2 Receptacle Connections

 

W

 

(GOLD)

 

(SILVER)

 

 

G

X

 

 

 

NEMA

 

NEMA

 

L5-30R

 

L14-30R

 

125V

125/250V

 

30A

 

30A

G

X

Y

W

NEMA 5-20R

(GOLD)

(GOLD)

(SILVER)

125V 20A

 

 

 

Frame Ground Connection

WARNING: Be sure the system is properly grounded before applying power. Do not apply AC power before you ensure that grounds are connected. Electrical shock can cause serious or fatal injury. NEC requires that the frame and exposed conductive surfaces (metal parts) be connected to an approved earth ground. Local codes may also require proper grounding of generator systems.

The NEC requires that the frame and exposed metal surfaces be at local ground reference potential to avoid electrical shock hazard. A local ground reference may require a driven earth ground conductor at the generator installation site. Make the ground connection as shown in Figure 3-3. Use the appropriate size wire (normally 6 AWG) as required by NEC and local codes. The local reference ground is normally a copper clad earth ground rod driven into the earth at least 8 feet.

WARNING: Do not connect the generator output neutral to the frame or local ground. The generator output is isolated from ground. NEC and local codes require that the generator output remain isolated from local ground reference.

Figure 3-3 Frame Ground Connection

Nut

Washer

Ground Wire Lug

Washer

Stud

Manual backgroundFrame

Earth Ground

MN2413

Receiving & Installation 3-3

Page 15
Image 15