Table 4-2 Three/Single Phase Operation

 

Alternator

Voltage

 

 

Voltage at Terminal Lugs

 

 

Voltage at Plug Receptacles

 

 

 

 

 

 

 

 

 

 

 

 

Switch

Line To Line Voltage

Line To Neutral Voltage

120VAC

240VAC Receptacles

Winding

Adjust

Position

Receptacles

(Twist Lock)

Connection

Position

 

 

 

 

 

 

 

 

 

 

 

L1−L2

L2−L3

 

L1−L3

L1−N

 

L2−N

L3−N

L−N

L−L

L−N

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Series High

Minimum

416

416

 

416

240

 

240

240

120

208

120

 

 

 

 

 

 

 

 

 

 

 

 

 

480/277

Middle

460

460

 

460

266

 

266

266

133

230

133

Wye

 

 

 

Maximum

480

480

 

480

277

 

277

277

139

240

139

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parallel Low

Minimum

208

208

 

208

120

 

120

120

120

208

120

 

 

 

 

 

 

 

 

 

 

 

 

 

208/120

Middle

230

230

 

230

133

 

133

133

133

230

133

Wye

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum

240

240

 

240

139

 

139

139

139

240

139

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parallel Low

Minimum





 

200

100

 



100

100

200

100

 

 

 

 

 

 

 

 

 

 

 

 

 

240/120

Middle





 

220

110

 



110

110

220

110

ZigZag

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum





 

240

120

 



120

120

240

120

 

 

 

 

No connection at Terminal Lug #2.

Receptacle Panel Load Connections, see Figure 4-4.

1.240/120VAC voltage is present at the receptacle panel at all times when generator is running.

2.Carefully inspect all Individual load cables for broken insulation or other signs of damage. Never use a damaged cable. Replace it before usage.

3.Individual load cables may be routed into the receptacle compartment through the Enclosure Electrical Access Panel.

4.Individual load cables may be connected or disconnected while generator is running. Use extreme care not to touch any electrical wire or terminal to avoid shock hazard.

5.Keep Enclosure Electrical Access Panel closed at all times. This prevents rain or other harmful elements from entering the compartment. Output metering and gauges can be observed through the window in the Enclosure Electrical Access Panel.

Figure 4-4 Receptacle Panel (Single Phase)

Circuit Breakers (Single or Double pole)

Circuit Breakers provides protection on some units. To reset a breaker, place it in the OFF then the ON position.

Note:

Single phase power is always available.

 

 

(GOLD)

(GOLD)

 

 

Y

X

 

 

X

 

 

 

CS6369

 

 

125/250V

Reset

Test

Y 50A

W

 

 

 

 

 

G

 

 

W

 

 

CS6365N

(SILVER)

 

GFI Outlet

240V, 50A

 

120V, 20A

 

 

Meters, switches, lights and other operator control components are located in various places on each panel. Figure 4-5can be used to identify the function and features of each operator control regardless of where it is located on your panel.

4-6 Operation

MN2417

Page 28
Image 28
Baldor TS45, TS25, TS60, TS400, TS80, TS175, TS130 Three/Single Phase Operation, Receptacle Panel Load Connections, see Figure