AlarmsFollowing alarms are available:
Sensor fail (FLS) see Table 4-5
Sensor fail is detected when measured value is 6% out of selected sensor characteristic. Sensor fail is indicated by ##### symbol instead measured value.
Warning (WRN) see Table
When warning comes up, only alarm outputs and common warning output are closed.
Shut down (SD) see Table 4-5
When the shut−down alarm comes up, InteliLite opens outputs GCB CLOSE/OPEN, FUEL SOLENOID, STARTER and PRESTART to stop the engine immediately. Alarm outputs and common shutdown output are closed. Active or not reset protection disables start.
| Table | ||
|
|
|
|
Events specification |
| Protection type | |
Wrn Oil press |
| WRN |
|
Sd Oil press |
| SD |
|
Wrn Water temp |
| WRN |
|
Sd Water temp |
| SD |
|
Wrn Wtemp Low |
| WRN |
|
Wrn Fuel Level |
| WRN |
|
Sd Fuel Level |
| SD |
|
Battery voltage <, > |
| WRN |
|
Battery flat |
| SD |
|
Start fail |
| SD |
|
Vgen <, > |
| SD |
|
Vgen unbl |
| SD |
|
Fgen <, > |
| SD |
|
Igen unbl |
| SD |
|
Overload |
| SD |
|
RPM over |
| SD |
|
RPM under |
| SD |
|
PickupFault |
| SD |
|
Stop fail |
| SD |
|
WrnServiceTime |
| WRN |
|
Emergency Stop |
| SD |
|
ECU Common Warning |
| WRN |
|
ECU Shutdown |
| SD |
|
MN2417 |