Analog Inputs Three analog inputs for resistive sensor 0 to 2400 ohms measuring are available on IL controller. Use LiteEdit software to modify configuration.

The Analog inputs values assignment (AI1 = Oil press, AI2 = Water temp, AI3 = Fuel level) is fix. It is possible to configure on each Analog input:

SReading from IL Analog inputs or from Engine Control Unit via CAN bus (J1939)

SSensor characteristics − from the list,

SValue dimension (e.g. psi − bars, °F − °C, % − l)

SNumber of decimal points (0, 1, 2, ...).

Note: Corresponding Analog input terminal is dead when reading is switched to ECU.

All values from ECU shall show ####, but no alarm is displayed when CAN communication is interrupted.

Warning and shut−down limits are adjusted in Engine protection group.

 

Table 4-8 Analog Inputs

 

 

 

AI1 Oil press

 

Oil pressure analog input. Default VDO sensor in range 0 to 145 psi.

AI2 Water temp

 

Water temperature analog input. Default VDO sensor in range 32 to 212°F

 

 

 

AI3 Fuel level

 

Fuel level analog input. Default VDO sensor 0−180R = 0−100%.

Set points

Table 4-9 Basic Setpoints

 

 

EnterPassword

Password is a four−digit number. Password enables change of relevant

 

protected set points Use or keys to set and ENTER key to enter the

 

password.

 

 

ChangePassword

Use or keys to set and ENTER key to change the password.

Gen−set name

User defined name, used for InteliLite identification at remote phone or

 

mobile connection. Gen−set name is max 14 characters long and have to

 

be entered using LiteEdit software.

 

 

Nomin power(3ph)

Nominal power of the generator in three phases connection.

 

Step: 1 kW; Range: 1 − 3000 kW

 

 

Nomin power(1ph)

Nominal power of the generator in single−phase connection.

 

Step: 1 kW; Range: 1 − 3000 kW

 

 

CT Ratio

Gen−set phases current transformers ratio.

 

Step: 1 A; Range: 1 − 5000 A / 5A

 

 

PT ratio

Gen−set potential transformers ratio.

 

Step: 0,1 V / V; Range: 0,1 − 500,0 V / V

 

 

Nominal freq

Nominal generator frequency (usually 50 or 60 Hz )

 

Step: 1Hz; Range: 45 − 65 Hz

 

 

Gear teeth

Number of teeth on the engine gear for the pick−up. Set to zero, if no

 

pick−up is used. Engine speed is counted from the generator frequency.

 

Step: 1; Range: 0 − 500

 

Note: Generator frequency can be used only when generator voltage

 

(min 5V) is present before reaching of the firing speed

 

(Starting RPM) after start.

Nominal RPM

Nominal engine speed. Step: 1RPM; Range: 100 − 4000 RPM.

FLTRESGOTOMAN

DISABLED: Controller stays in AUT mode after Fault reset .

 

ENABLED: Automatic switch from AUT (or TEST) to MAN mode after

 

Fault reset to avoid automatic engine start. This function is active for Shut

 

down protection only.

 

 

DispBackLightTO

Timeout after which the display backlight is switched off.

 

Step: 1 min Range: 0 − 60 min

 

Default value: 0 = the display lights all the time

 

 

Mode IL [ OFF, MAN, AUT ]

Equivalent to Controller mode changes by MODE" or MODEA buttons.

 

Note: Controller Mode change can be separately password protected.

 

 

RS232 mode

Communication protocol switch.

[Standard/Modbus ]

Standard: LiteEdit communication protocol. Modbus: Modbus protocol.

 

Note: For detail description see chapter Modbus protocol.

 

 

Num rings AA

Number of rings prior to open modem connection. Step: 1; Range: 1 − 30

 

Note: NumberRings AA change is not activated immediately. It is activated

 

after controller is switched on or when modem is connected to controller.

4-14 Operation

MN2417

Page 36
Image 36
Baldor TS45, TS60, TS400, TS80, TS175, TS130, TS35, TS250 manual Analog Inputs, Set points Basic Setpoints