WIRING – MAIN POWER

Refer to the unit rating plate for wire sizing information and maximum fuse or “HACR” type circuit breaker size. Each outdoor unit is marked with a “Minimum Circuit Ampacity”. This means that the field wiring used must be sized to carry that amount of current. Depending on the installed KW of electric heat, there may be two field power circuits required. If this is the case, the unit serial plate will so indicate. All models are suitable only for connection with copper wire. Each unit and/or wiring diagram will be marked “Use Copper Conductors Only”. These instructions must be adhered to. Refer to the National Electrical Code (NEC) for complete current carrying capacity data on the various insulation grades of wiring material. All wiring must conform to NEC and all local codes.

The electrical data lists fuse and wire sizes (75° C copper) for all models including the most commonly used heater sizes. Also shown are the number of field power circuits required for the various models with heaters.

The unit rating plate lists a “Maximum Time Delay Relay Fuse” or “HACR” type circuit breaker that is to be used with the equipment. The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high starting current of the compressor motor.

The disconnect access door on this unit may be locked to prevent unauthorized access to the disconnect. To convert for the locking capability, bend the tab located in the bottom left-hand corner of the disconnect opening under the disconnect access panel straight out. This tab will now line up with the slot in the door. When shut, a padlock may be placed through the hole in the tab preventing entry.

See “Start Up” section for important information on three phase scroll compressor start ups.

See Tables 4 & 5 for Electrical Specifications.

WIRING – LOW VOLTAGE WIRING

230/208V, 1 phase and 3 phase equipment dual primary voltage transformers. All equipment leaves the factory wired on 240V tap. For 208V operation, reconnect from 240V to 208V tap. The acceptable operating voltage range for the 240 and 208V taps are:

TAP

RANGE

240

253 – 216

208

220 – 187

NOTE: The voltage should be measured at the field power connection point in the unit and while the unit is operating at full load (maximum amperage operating condition).

For wiring size and connections, refer to Wiring Manual 2100-507.

Manual

2100-508A

Page

14 of 25

Page 14
Image 14
Bard W70L1, 1 W48A1, W42L, W70A1 installation instructions Wiring Main Power, Wiring LOW Voltage Wiring, TAP Range

W70A1, W70L1, W42L, 1 W48A1 specifications

The Bard range of products, specifically the W24L1, W48L1, W42L1, W70A1, and W60A1 models, showcases advanced engineering aimed at providing efficient heating and cooling solutions. Each model comes with distinctive features and technologies tailored to meet various residential and commercial needs.

Starting with the W24L1 model, it is designed for compact spaces while delivering powerful performance. Its heating capacity is optimal for smaller areas, making it suitable for residential applications. The W24L1 incorporates advanced inverter technology, ensuring energy efficiency and reducing operational costs. This model is equipped with a user-friendly interface, enabling easy control and monitoring of settings.

Next is the W48L1, which offers increased capacity for larger spaces. This model is characterized by its robust build and enhanced airflow system that ensures uniform heating and cooling throughout the environment. The W48L1 utilizes environmentally friendly refrigerants, highlighting Bard’s commitment to sustainability. Its smart technology integration allows for seamless compatibility with smart home systems, providing added convenience for users.

The W42L1 model stands out for its versatility in both heating and cooling applications. It is engineered with high-efficiency components, which contribute to lower energy consumption. Features like programmable thermostats and variable speed fans enhance user comfort and adjust to varying demand. The W42L1 also comes with a durable construction, ensuring longevity and reliability even in challenging conditions.

For those demanding even higher performance, the W70A1 model caters to significant heating and cooling requirements. This unit is designed to tackle extreme weather conditions and is often favored for industrial applications. The W70A1 employs advanced heat exchanger technology, improving efficiency and reducing energy loss. Moreover, its rugged design enables operation in harsh environments without compromising performance.

Lastly, the W60A1 represents a harmonious blend of efficiency and power. It is particularly well-suited for mid-sized applications, combining the best features from the other models. The W60A1 integrates sophisticated microprocessor controls that optimize performance while ensuring compatibility with emerging smart technology platforms. Its energy-efficient design means lower operating costs while delivering impressive comfort levels.

In summary, Bard's W24L1, W48L1, W42L1, W70A1, and W60A1 models are engineered to deliver superior heating and cooling solutions across a variety of environments. With a focus on energy efficiency, advanced technologies, and user-friendly interfaces, these models exemplify Bard's commitment to innovation and sustainability in climate control systems.