TABLE 5

Electrical Specifications — W**L Series

 

 

 

 

Single Circuit

 

 

 

 

Dual Circuit

 

 

 

 

Rated

No. Field

3 Minimum

1 Maximum

2 Field

 

3 Minimum

1 Maximum

2 Field

2 Ground

 

2 Ground

Circuit

External Fuse

Power

Model

Volts

Power

Circuit

External Fuse

Power

Wire Size

Wire

Ampacity

or Ckt. Brkr.

Wire Size

 

and Phase

Circuits

Ampacity

or Ckt. Brkr.

Wire Size

 

 

 

 

 

 

 

 

 

Ckt. A

Ckt. B

Ckt. A

Ckt. B

Ckt. A

Ckt. B

Ckt. A

Ckt. B

W18L1 - A00, A0Z

 

1

16

20

12

12

 

 

 

 

 

 

 

 

A05

230/208-1

1

30

30

10

10

 

 

 

 

 

 

 

 

A08

1

46

50

8

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A10

 

1

56

60

6

10

 

 

 

 

 

 

 

 

W24L1 - A00, A0Z

 

1

21

30

10

10

 

 

 

 

 

 

 

 

A05

230/208-1

1

30

30

10

10

 

 

 

 

 

 

 

 

A08

1

46

50

8

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A10

 

1

56

60

6

10

 

 

 

 

 

 

 

 

W24L1 - B00, B0Z

230/208-3

1

15

15

14

14

 

 

 

 

 

 

 

 

B06

1

22

25

10

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

W30L1 - A00*, A0Z*

 

1

24

35

8

10

 

 

 

 

 

 

 

 

A05*

 

1

32

35

8

10

 

 

 

 

 

 

 

 

A08

230/208-1

1

48

50

8

10

 

 

 

 

 

 

 

 

A10*

 

1

58

60

6

10

 

 

 

 

 

 

 

 

A15

 

1 or 2

84

90

4

8

58

26

60

30

6

10

10

10

W30L1 - B00*, B0Z*

 

1

18

20

12

12

 

 

 

 

 

 

 

 

B09*

230/208-3

1

33

35

8

10

 

 

 

 

 

 

 

 

B15

 

1

51

60

8

10

 

 

 

 

 

 

 

 

W30L1 - C00*, C0Z*

 

1

11

15

14

14

 

 

 

 

 

 

 

 

C09*

460-3

1

17

20

12

12

 

 

 

 

 

 

 

 

C15

 

1

26

30

10

10

 

 

 

 

 

 

 

 

W36L1 - A00*, A0Z*

 

1

29

35

8

10

 

 

 

 

 

 

 

 

A05*

230/208-1

1

32

35

8

10

 

 

 

 

 

 

 

 

A10*

1

58

60

6

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A15

 

1 or 2

84

90

4

8

58

26

60

30

6

10

10

10

W36L1 - B00*, B0Z*

 

1

23

30

10

10

 

 

 

 

 

 

 

 

B09*

230/208-3

1

33

35

8

10

 

 

 

 

 

 

 

 

B15

 

1

51

60

6

10

 

 

 

 

 

 

 

 

W36L1 - C00*, C0Z*

 

1

12

15

14

14

 

 

 

 

 

 

 

 

C09*

460-3

1

17

20

10

10

 

 

 

 

 

 

 

 

C15

 

1

26

30

10

10

 

 

 

 

 

 

 

 

W42L1 - A00, A0Z

 

1

33

50

8

10

 

 

 

 

 

 

 

 

A05

230/208-1

1

33

50

8

10

 

 

 

 

 

 

 

 

A10

1

59

60

6

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A15

 

1 or 2

85

90

4

8

59

26

60

30

6

10

10

10

W42L1 - B00, B0Z

 

1

25

35

8

10

 

 

 

 

 

 

 

 

B09

230/208-3

1

34

35

8

10

 

 

 

 

 

 

 

 

B15

 

1

53

60

6

10

 

 

 

 

 

 

 

 

W42L1 - C00, C0Z

 

1

13

15

14

14

 

 

 

 

 

 

 

 

C09

460-3

1

18

20

12

12

 

 

 

 

 

 

 

 

C15

 

1

27

30

10

10

 

 

 

 

 

 

 

 

W48L1 - A00, A0Z

 

1

37

50

8

10

 

 

 

 

 

 

 

 

A05

230/208-1

1

37

50

8

10

 

 

 

 

 

 

 

 

A10

1

59

60

6

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A15

 

1 or 2

85

90

4

8

59

26

60

30

6

10

10

10

W48L1- B00, B0Z

 

1

29

40

8

10

 

 

 

 

 

 

 

 

B09

230/208-3

1

34

40

8

10

 

 

 

 

 

 

 

 

B15

 

1

52

60

6

10

 

 

 

 

 

 

 

 

W48L1 - C00, C0Z

 

1

14

20

12

12

 

 

 

 

 

 

 

 

C09

460-3

1

18

20

12

12

 

 

 

 

 

 

 

 

C15

 

1

27

30

10

10

 

 

 

 

 

 

 

 

W60L1 - A00, A0Z

 

1

41

60

8

10

 

 

 

 

 

 

 

 

A05

230/208-1

1

41

60

8

10

 

 

 

 

 

 

 

 

A10

1

59

60

6

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A15

 

1 or 2

85

90

4

8

59

26

60

30

6

10

10

10

W60L1 - B00, B0Z

 

1

28

40

8

10

 

 

 

 

 

 

 

 

B09

230/208-3

1

34

40

8

10

 

 

 

 

 

 

 

 

B15

 

1

53

60

6

10

 

 

 

 

 

 

 

 

W60L1 - C00, C0Z

 

1

15

20

12

12

 

 

 

 

 

 

 

 

C09

460-3

1

18

20

12

12

 

 

 

 

 

 

 

 

C15

 

1

27

30

10

10

 

 

 

 

 

 

 

 

W70L1 - A0Z

 

1

49

60

8

10

 

 

 

 

 

 

 

 

A05

230/208-1

1

49

60

8

10

 

 

 

 

 

 

 

 

A10

1 or 2

59

60

6

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A15

 

1 or 2

85

90

4

8

59

26

60

30

6

10

10

10

W70L1 - B0Z

 

1

43

60

8

10

 

 

 

 

 

 

 

 

B09

230/208-3

1

43

60

8

10

 

 

 

 

 

 

 

 

B15

 

1

53

60

6

10

 

 

 

 

 

 

 

 

W70L1 - C0Z

 

1

23

30

10

10

 

 

 

 

 

 

 

 

C09

460-3

1

23

30

10

10

 

 

 

 

 

 

 

 

C15

 

1

27

35

8

10

 

 

 

 

 

 

 

 

1Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors.

2 Based on 75C copper wire. All wiring must conform to the National Electrical Code and all local codes.

3 These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electrical code (latest version), Article 310 for power conductor sizing.

Caution: When more than one field power circuit is run through one conduit, the conductors must be derated. Pay special attention to note 8 of Table 310 regarding Ampacity Adjustment Factors when more than three (3) current carrying conductors are in a raceway.

* Top outlet supply option is available only factory installed and only on the selected models.

IMPORTANT: While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses and conductor wires in accordance with the National Electrical Code and all local codes.

Manual

2100-508A

Page

21 of 25

Page 21
Image 21
Bard W42L, 1 W48A1, W70L1, W70A1 Electrical Specifications - W**L Series, Manual, 2100-508A, Page, 21 of