Bard PH1224, PH1230, PH1236 Trouble Shooting Guide, Symptom, Possible Causes, What to Check

Models: PH1224 PH1236 PH1230

1 23
Download 23 pages 37.95 Kb
Page 17
Image 17
TROUBLE SHOOTING GUIDE

TROUBLE SHOOTING GUIDE

Symptom

Possible Causes

What to Check

How to Check or Repair

 

 

 

 

Compressor contactor

Contil circuit wiring

Check for R connection at unit

Run R connection to outdoor unit to power heat

does not energize

 

and 24 volt between R-C.

pump control.

(heating or cooling)

 

 

 

Compressor lock out

1. Check for 24V between

1. If no voltage between L1-C, turn thermostat off

 

 

 

L1-C on heat pump control

and on again to reset high pressure switch.

 

 

2. Check across high

2. If high pressure switch is open and will not reset,

 

 

pressure switch.

replace high pressure switch.

 

 

 

 

 

Compressor short cycle

Check for 24V between CC-C

If no voltage between CC-C, jumper speed up

 

protection

and Y-C on heat pump

terminal, and within 10 seconds power should

 

 

control.

appear between CC-C. Remove speed up jumper

 

 

 

after 10 seconds.

 

 

 

 

 

Heat pump control

Check all other possible

Replace heat pump control.

 

defective

causes. Manual 2100-065.

 

 

 

 

 

 

Contactor defective

Check for open or shorted

Replace contactor.

 

 

coil winding.

 

 

 

 

 

Fan outdoor motor

Motor defective

Check for open or shorted

Replace motor.

does not run

 

motor winding.

 

(cooling or heating

 

 

 

Motor capacitor defective

Check capacitor rating.

Replace capacitor.

except during defrost)

 

Check for open or shorted

 

 

 

 

 

 

capacitor.

 

 

 

 

 

 

Heat pump control

Check across fan relay on

Replace heat pump control.

 

defective

heat pump control. (Com-NC)

 

 

 

 

 

Reversing valve does

Reversing volve solenoid

Check for open or shorted

Replace solenoid coil.

not energize

coil defective

coil.

 

(heating only)

 

 

 

Heat pump control

Check for 24V between RV-C

1. Check control circuit wiring.

 

 

defective

and B-C.

2. Replace heat pump control

 

 

 

 

Unit will not go into

Temperature sensor or

Disconnect temperature

1. If unit goes through defrost cycle, replace

defrost

heat pump control

sensor from board and

temperature sensor.

(heating only)

defective

jumper across speed up

 

 

 

terminals and sen jump

2. If unit does not go through defrost cycle, replace

 

 

terminals. This should cause

heat pump control.

 

 

the unit to go through a

 

 

 

defrost cycle within one

 

 

 

minute.

 

 

 

 

 

Unit will not come out

Temperature sensor or

Jumper across speed up

1. If unit comes out of defrost cycle, replace

of defrost

heat pump control

terminals. This should cause

temperature sensor.

(heating only)

defective.

the unit to come out of defrost

2. If unit does not come out of defrost cycle,

 

 

within one minute.

replace heat pump control.

 

 

 

 

Manual 2100-344 Page 15

Page 17
Image 17
Bard PH1224, PH1230, PH1236 Trouble Shooting Guide, Symptom, Possible Causes, What to Check, How to Check or Repair