Bard PH1224, PH1230, PH1236 installation instructions Pressure Tables Table Cooling

Models: PH1224 PH1236 PH1230

1 23
Download 23 pages 37.95 Kb
Page 20
Image 20
PRESSURE TABLES

PRESSURE TABLES

TABLE 11

COOLING

Air Temperature Entering Outdoor Coil Degrees F

 

Return Air

 

 

 

 

 

 

 

 

 

 

Model

Temperature

Pressure

75

80

85

90

95

100

105

110

115

 

 

 

 

 

 

 

 

 

 

 

 

 

75 deg. DB

Low Side

73

75

76

78

79

80

81

82

83

 

62 deg. WB

High Side

191

205

219

234

251

267

285

303

323

 

 

 

 

 

 

 

 

 

 

 

 

PH1224

80 deg. DB

Low Side

78

80

81

83

84

88

87

88

89

67 deg. WB

High Side

196

210

225

240

257

274

292

311

331

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85 deg. DB

Low Side

81

83

84

86

87

89

90

91

92

 

72 deg. WB

High Side

203

217

233

248

266

284

302

322

343

 

 

 

 

 

 

 

 

 

 

 

 

 

75 deg. DB

Low Side

73

75

76

78

79

79

81

82

84

 

62 deg. WB

High Side

208

222

237

254

270

288

307

326

346

 

 

 

 

 

 

 

 

 

 

 

 

PH1230

80 deg. DB

Low Side

78

80

81

83

84

85

87

88

90

67 deg. WB

High Side

213

228

243

260

277

295

315

334

355

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85 deg. DB

Low Side

81

83

84

86

87

88

90

91

93

 

72 deg. WB

High Side

220

236

252

269

287

305

326

346

367

 

 

 

 

 

 

 

 

 

 

 

 

 

75 deg. DB

Low Side

72

74

75

77

78

79

80

81

82

 

62 deg. WB

High Side

211

225

242

258

276

294

314

333

355

 

 

 

 

 

 

 

 

 

 

 

 

PH1236

80 deg. DB

Low Side

77

79

80

82

83

84

86

87

88

67 deg. WB

High Side

216

231

248

265

283

302

322

342

364

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85 deg. DB

Low Side

80

82

83

85

86

87

89

90

91

 

72 deg. WB

High Side

224

239

257

274

293

313

333

354

377

 

 

 

 

 

 

 

 

 

 

 

 

TABLE 12

HEATING

Air Temperature Entering Outdoor Coil Degrees F

 

Return

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Model

Air Temp.

Pressure

0

5

10

15

17

20

25

30

35

40

45

47

50

55

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PH1224

70 deg

Low Side

22

24

27

30

31

33

37

41

45

50

56

58

62

68

High Side

174

182

190

198

201

205

213

221

229

237

245

248

253

261

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PH1230

70 deg

Low Side

21

23

25

28

29

31

34

38

43

48

53

55

59

65

High Side

167

170

174

178

179

182

187

192

197

203

210

213

217

224

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PH1236

70 deg

Low Side

24

25

26

28

28

30

33

37

42

47

53

56

60

68

High Side

194

195

197

201

202

205

211

218

226

235

246

250

257

270

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low side pressure ± 2 PSIG

High side pressure ± 5 PSIG

Tables are based upon rated CFM (airflow across the evaporator coil and should be found under section titled “Refrigerant Charge” elsewhere in manual. If there is any doubt as to correct operating charge being in the system, the charge should be removed, system evacuated, and recharged to serial plate instructions.