PRESSURE TABLES
TABLE 11
COOLING
Air Temperature Entering Outdoor Coil Degrees F
| Return Air |
|
|
|
|
|
|
|
|
|
| |
Model | Temperature | Pressure | 75 | 80 | 85 | 90 | 95 | 100 | 105 | 110 | 115 | |
|
|
|
|
|
|
|
|
|
|
|
| |
| 75 deg. DB | Low Side | 73 | 75 | 76 | 78 | 79 | 80 | 81 | 82 | 83 | |
| 62 deg. WB | High Side | 191 | 205 | 219 | 234 | 251 | 267 | 285 | 303 | 323 | |
|
|
|
|
|
|
|
|
|
|
|
| |
PH1224 | 80 deg. DB | Low Side | 78 | 80 | 81 | 83 | 84 | 88 | 87 | 88 | 89 | |
67 deg. WB | High Side | 196 | 210 | 225 | 240 | 257 | 274 | 292 | 311 | 331 | ||
| ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
| |
| 85 deg. DB | Low Side | 81 | 83 | 84 | 86 | 87 | 89 | 90 | 91 | 92 | |
| 72 deg. WB | High Side | 203 | 217 | 233 | 248 | 266 | 284 | 302 | 322 | 343 | |
|
|
|
|
|
|
|
|
|
|
|
| |
| 75 deg. DB | Low Side | 73 | 75 | 76 | 78 | 79 | 79 | 81 | 82 | 84 | |
| 62 deg. WB | High Side | 208 | 222 | 237 | 254 | 270 | 288 | 307 | 326 | 346 | |
|
|
|
|
|
|
|
|
|
|
|
| |
PH1230 | 80 deg. DB | Low Side | 78 | 80 | 81 | 83 | 84 | 85 | 87 | 88 | 90 | |
67 deg. WB | High Side | 213 | 228 | 243 | 260 | 277 | 295 | 315 | 334 | 355 | ||
| ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
| |
| 85 deg. DB | Low Side | 81 | 83 | 84 | 86 | 87 | 88 | 90 | 91 | 93 | |
| 72 deg. WB | High Side | 220 | 236 | 252 | 269 | 287 | 305 | 326 | 346 | 367 | |
|
|
|
|
|
|
|
|
|
|
|
| |
| 75 deg. DB | Low Side | 72 | 74 | 75 | 77 | 78 | 79 | 80 | 81 | 82 | |
| 62 deg. WB | High Side | 211 | 225 | 242 | 258 | 276 | 294 | 314 | 333 | 355 | |
|
|
|
|
|
|
|
|
|
|
|
| |
PH1236 | 80 deg. DB | Low Side | 77 | 79 | 80 | 82 | 83 | 84 | 86 | 87 | 88 | |
67 deg. WB | High Side | 216 | 231 | 248 | 265 | 283 | 302 | 322 | 342 | 364 | ||
| ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
| |
| 85 deg. DB | Low Side | 80 | 82 | 83 | 85 | 86 | 87 | 89 | 90 | 91 | |
| 72 deg. WB | High Side | 224 | 239 | 257 | 274 | 293 | 313 | 333 | 354 | 377 | |
|
|
|
|
|
|
|
|
|
|
|
|
TABLE 12
HEATING
Air Temperature Entering Outdoor Coil Degrees F
| Return |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Model | Air Temp. | Pressure | 0 | 5 | 10 | 15 | 17 | 20 | 25 | 30 | 35 | 40 | 45 | 47 | 50 | 55 | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
PH1224 | 70 deg | Low Side | 22 | 24 | 27 | 30 | 31 | 33 | 37 | 41 | 45 | 50 | 56 | 58 | 62 | 68 | |
High Side | 174 | 182 | 190 | 198 | 201 | 205 | 213 | 221 | 229 | 237 | 245 | 248 | 253 | 261 | |||
|
| ||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
PH1230 | 70 deg | Low Side | 21 | 23 | 25 | 28 | 29 | 31 | 34 | 38 | 43 | 48 | 53 | 55 | 59 | 65 | |
High Side | 167 | 170 | 174 | 178 | 179 | 182 | 187 | 192 | 197 | 203 | 210 | 213 | 217 | 224 | |||
|
| ||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
PH1236 | 70 deg | Low Side | 24 | 25 | 26 | 28 | 28 | 30 | 33 | 37 | 42 | 47 | 53 | 56 | 60 | 68 | |
High Side | 194 | 195 | 197 | 201 | 202 | 205 | 211 | 218 | 226 | 235 | 246 | 250 | 257 | 270 | |||
|
| ||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Low side pressure ± 2 PSIG
High side pressure ± 5 PSIG
Tables are based upon rated CFM (airflow across the evaporator coil and should be found under section titled “Refrigerant Charge” elsewhere in manual. If there is any doubt as to correct operating charge being in the system, the charge should be removed, system evacuated, and recharged to serial plate instructions.
Manual