Bard PH1236, PH1230, PH1224 Service And Troubleshooting, Service Hints, Pressure Service Ports

Models: PH1224 PH1236 PH1230

1 23
Download 23 pages 37.95 Kb
Page 16
Image 16
SERVICE AND TROUBLESHOOTING

SERVICE AND TROUBLESHOOTING

SERVICE HINTS

1.Caution homeowner to maintain clean air filters at all times. Also, not to needlessly close off supply and return air registers. This reduces air flow through the system which shortens equipment service life as well as increasing operating costs.

2.Switching to heating cycle at 75° F or higher outside temperature may cause a nuisance trip of the manual reset high pressure switch.

3.The heat pump wall thermostats perform multiple functions. Be sure that all function switches are correctly set for the desired operating mode before trying to diagnose any reported service problems.

4.Check all power fuses or circuit breakers to be sure that they are the correct rating.

5.Periodic cleaning of the outdoor coil to permit full and unrestricted airflow circulation is essential.

PRESSURE SERVICE PORTS

High and low pressure service ports are installed on all units so that the system operating pressures can be observed. Pressure tables can be found in Tables 11 and 12 in this manual covering all models on both cooling and heating cycles. It is imperative to match the correct pressure table to the unit by model number.

REFRIGERANT CHARGE

The correct system R-22 charge is shown on the unit rating plate. Optimum unit performance will occur with a refrigerant charge resulting in a suction line temperature (6” from compressor) as shown in Table 10.

TABLE 10

 

 

95 Degree F

82 Degree F

 

Rated

 

OD

 

 

OD

 

Model

Airflow

Temperature

Temperature

 

 

 

 

 

 

 

 

PH1224

800

56

-

56

61

-

62

PH1230

1000

56

-

56

58

-

60

PH1236

1100

50

-

52

52

-

54

 

 

 

 

 

 

 

 

The above suction line temperatures are based upon 80° F dry bulb/67° F wet bulb (50% RH) temperature and rated airflow across the evaporator during cooling cycle.

FAN BLADE SETTINGS

Shown in Figure 12 are the correct fan blade setting dimensions for proper air delivery across the outdoor coil.

Any service work requiring removal or adjustment in the fan and/or motor area will require that the dimensions in Figure 12 be checked and blade adjusted in or out on the motor shaft accordingly.

FIGURE 12

FAN BLADE SETTING DIMENSIONS

Model

Dimension A

 

 

PH1224

1.00"

PH1230

.75"

PH1236

.75"

 

 

MIS-1190

SOLID STATE HEAT PUMP CONTROL TROUBLESHOOTING PROCEDURE

1.Turn on AC power supply to indoor and outdoor units.

2.Turn thermostat blower switch to fan on. The indoor blower should start. (If it doesn’t, troubleshoot indoor unit and correct problem.)

3.Turn thermostat blower switch to Auto position. Indoor blower should stop.

4.Set system switch to heat or cool. Adjust thermostat to call for heat or cool. The indoor blower, compressor, and outdoor fan should start.

NOTE: If there is no power to 24 volt transformer, the compressor and outdoor fan motor will not start for 5 minutes. This is because of the compressor short cycle protection.

Manual 2100-344 Page 14

Page 16
Image 16
Bard PH1236 Service And Troubleshooting, Service Hints, Pressure Service Ports, Refrigerant Charge, Fan Blade Settings