TABLE 1
ELECTRICAL DATA
|
|
|
| Q |
|
|
|
|
|
|
| Maximum |
| R |
|
|
|
|
| External | Minimum | Field | R |
| Rated | Operating |
| Fuses or | Circuit | Power | Ground |
|
| Ckt. Brk. | Ampacity | Wiring | Wire Size | ||
| Volts & | Voltage | Maximum | ||||
|
|
|
|
| |||
|
|
|
|
| |||
Model | Phases | Range | Unit Amps | Ckt. A | Ckt. A | Ckt. A | Ckt. A |
|
|
|
|
|
|
|
|
PH1224 | 197 - 253 | 14.4 | 25 | 18 | 10 | 10 | |
|
|
|
|
|
|
|
|
PH1230 | 197 - 253 | 17.7 | 30 | 22 | 10 | 10 | |
|
|
|
|
|
|
|
|
PH1236 | 197 - 253 | 21.8 | 40 | 27 | 8 | 8 | |
|
|
|
|
|
|
|
|
197 - 253 | 15.6 | 25 | 19 | 10 | 10 | ||
|
|
|
|
|
|
|
|
QMaximum time delay fuse or HACR type circuit breaker. HACR type not applicable to 460 volt.
R75 degree C cooper wire size, basic unit only.
TABLE 2
OPTIONAL FIELD INSTALLED HEATER PACKAGES
ONLY TO BE USED WITH THE HEAT PUMP MODELS INDICATED
Heater Package | Volts and |
|
|
|
|
Model No. | Phase | PH1224 | PH1230 | PH1236 | |
|
|
|
|
|
|
| X | X | X |
| |
240/1 |
| X | X |
| |
X |
|
|
| ||
|
|
|
| ||
|
| X | X |
| |
|
|
|
|
|
|
240/3 |
|
|
| X | |
|
|
| X | ||
|
|
|
| ||
|
|
|
|
|
|
TABLE 3
OPTIONAL
|
| Htr. KW & |
|
|
|
|
|
| Circuit B |
|
| ||
|
| Capacity |
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
| |||
|
| @ 240V (or | Htr. KW & | @ 240V |
|
|
|
|
|
| |||
|
|
|
|
| Q | R | S | ||||||
|
| 480V if | Capacity |
|
|
| |||||||
Heater |
| or 480V as | Heater | No. | Minimum | Maximum | Field | Ground | |||||
| applicable) | @ 208 Volts | |||||||||||
Pkg. Model | Unit Volts | applicable | Internal | Field | Circuit | Overcurrent | Power | Wire | |||||
|
|
|
| ||||||||||
No. | Phase | KW | BTUH | KW | BTUH | Htr. Amps | Fuses | Ckts. | Ampacity | Protection | Wiring | Size | |
|
|
|
|
|
|
|
|
|
|
|
|
| |
10 | 34,100 | 7.50 | 26,000 | 41.7 |
| 1 | 53 | 60 | 6 | 10 | |||
|
|
|
|
|
|
|
|
|
|
|
|
| |
5 | 17,100 | 3.75 | 12,800 | 20.8 |
| 1 | 26 | 30 | 10 | 10 | |||
10 | 34,100 | 7.50 | 26,000 | 41.7 |
| 1 | 53 | 60 | 6 | 10 | |||
15 | 51,200 | 11.25 | 38,400 | 62.5 | 30/60 | 1 | 79 | 80 | 4 | 8 | |||
|
|
|
|
|
|
|
|
|
|
|
|
| |
9 | 30,700 | 6.75 | 23,000 | 21.7 |
| 1 | 28 | 30 | 10 | 10 | |||
15 | 51,200 | 11.25 | 38,400 | 36.2 |
| 1 | 46 | 50 | 8 | 10 | |||
|
|
|
|
|
|
|
|
|
|
|
|
|
QTime delay fuses or “HACR” type circuit breakers must be used for 60 and smaller sizes. Standard fuses or circuit breakers are suitable for sizes 70 and larger. 480V circuit breakers are not “HACR” type.
RBased on wire suitable for 75° C. Other wiring materials must be rated for marked “Minimum Circuit Ampacity” or greater.
SBased upon Table
IMPORTANT: While this electrical data is presented as a guide, it is important to electrically connect properly size fuses and conductor wires in accordance with the National Electrical Code and all existing local codes.