TABLE 4

RECOMMENDED AIRFLOW

 

Rated

Rated

Recommended

Model

CFM *

ESP *

Airflow Range

 

 

 

 

W3R/LV

1100

.15

1100 - 550

 

 

 

 

W5R/LV

1700

.20

1700 - 850

 

 

 

 

W6R/LV

1700

.20

1700 - 850

 

 

 

 

* Rated CFM and ESP on high speed tap.

TABLE 5

MAXIMUM ESP OF OPERATION

ELECTRIC HEAT ONLY

 

W3

W5, W6

 

 

 

Model

FRONT

FRONT

 

 

 

 

High

High

 

 

 

-A0Z

.50

.50

-A05

.50

.50

-A10

.50

.50

 

 

 

-B0Z

.50

.50

-B06

.50

.50

-B09

.50

.50

 

 

 

-C0Z

.50

.50

-C09

.50

.50

-C12

.45

.50

 

 

 

Values shown are for units equipped with standard 1-inch throwaway filter or 1-inch washable filter. Derate ESP by .15 for 2-inch pleated filters.

TABLE 6

ELECTRIC HEAT

Models

240V-1

208V-1

240V-3

208V-3

460V-3

 

 

 

 

 

 

 

 

 

 

 

KW

Amps

BTUH

Amps

BTUH

Amps

BTUH

Amps

BTUH

Amps

BTUH

 

 

 

 

 

 

 

 

 

 

 

4

16.7

13650

14.4

10240

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

20.8

17065

18.1

12800

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

 

 

 

14.4

20500

12.5

15360

7.2

20500

 

 

 

 

 

 

 

 

 

 

 

8

33.3

27300

28.8

20475

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

 

 

 

 

21.7

30600

18.7

23030

10.8

30700

 

 

 

 

 

 

 

 

 

 

 

10

41.6

34130

36.2

25600

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

 

 

 

 

 

 

 

 

14.4

40950

 

 

 

 

 

 

 

 

 

 

 

15

62.5

51250

54.0

38400

36.2

51200

31.2

38400

18.0

51200

 

 

 

 

 

 

 

 

 

 

 

18

 

 

 

 

43.3

61430

37.5

46100

 

 

 

 

 

 

 

 

 

 

 

 

 

20

83.2

68260

72.1

51200

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Manual

2100-538E

Page

22 of 23

Page 22
Image 22
Bard W6LV1, W6RV1, W3RV1, W5LV1, W3LV1, W5RV1 Recommended Airflow, Maximum ESP of Operation Electric Heat only