Bard WA5S Capacity and Efficiency Ratings, Indoor Blower Performance - CFM 0.00 through 0.80 H2O

Models: WA3S WA5S WL5S WL3S

1 12
Download 12 pages 28.93 Kb
Page 2
Image 2
Capacity and Efficiency Ratings 1

Capacity and Efficiency Ratings 1

MODELS

Cooling Capacity BTUH, 2nd Stage Operation EER 2nd Stage Operation 12

Rated CFM (Wet Coil)

Cooling Capacity BTUH, 1st Stage Operation EER 1st Stage Operation 2

Rated CFM (Wet Coil)

IPLV 3

WA3S3

WL3S2

35,400

11.1

1100

24,000

11.7

800

15.1

WA4S3

WL4S2

46,000

11.2

1500

34,000

11.6

1100

15.2

WA5S3

WL5S2

56,500

10.1

1700

40,000

10.8

1300

14.3

1 Certified in accordance with ANSI/ARI Standard 390-2003 for single package vertical units.

2 EER = Energy Efficiency Ratio - BTU/WATT efficiency.

3 Integrated Part Load Value - BTU/WATT efficiency and certified in accordance with ANSI/ARI Standard 390-2003.

All capacity, efficiency and cost of operation information is based on operation with fresh air cover plate. Cover plate is recommended for use to obtain maximum energy efficiency where ventilation air is not required.

Indoor Blower Performance - CFM (0.00" through 0.80" H2O) 1

 

Blower Only

1st Stage Cooling

2nd Stage Cooling

5-10 KW Electric

15-20 KW Electric

 

 

 

 

Heat

Heat

 

 

 

 

 

 

WA3S3

800

800

1100

1100

1400

WL3S2

 

 

 

 

 

 

 

 

 

 

 

WA4S3

825

1100

1500

1100

1500

WL4S2

 

 

 

 

 

WA5S3

850

1300

1700

1100

1500

WL5S2

 

 

 

 

 

 

 

 

 

 

 

1 These systems contain Variable Speed ECM Motor, which maintains airflow across static range at dry and wet coil conditions.

Specifications 3 Ton through 5 Ton

MODELS

Cooling Capacity

Heating Capacity

WA3S3-A

WA3S3-B

WA3S3-C

WA4S3-A

WA4S3-B

WA4S3-C

WA5S3-A

WA5S3-B

WA5S3-C

WL3S2-A

WL3S2-B

WL3S2-C

WL4S2-A

WL4S2-B

WL4S2-C

WL5S2-A

WL5S2-B

WL5S2-C

35,400

35,400

35,400

46,000

46,000

46,000

56,500

56,500

56,500

 

 

 

 

 

 

 

 

 

See Electric Heat Table

Electrical Rating--60 Hz

Operating Voltage Range

Compressor--Circuit A

Voltage

Rated Load Amps

Branch Circuit Selection Current

Lock Rotor Amps

Compressor Type

Fan Motor & Condenser

Fan Motor--HP-RPM-SPD

Fan Motor--Amps

Fan--DIA/CFM

230/208-1

230/208-3

197-253

197-253

230/208

230/208

12.3/14.6

6.7/7.9

16.711.6

83

73

Scroll

Scroll

1/3-825-2 1/3-825-2

2.52.5

24" - 2700 24" - 2700

460-3

230/208-1

230/208-3

 

460-3

 

230/208-1

 

230/208-3

460-3

414-506

197-253

197-253

 

414-506

 

197-253

 

197-253

414-506

460

 

230/208

 

460

 

230/208

 

230/208

460

230/208

 

 

 

3.6

16.1/19.1

10.1/12

 

4.8

 

21.9/26.6

 

15.5/18.9

7.8

5.7

21.2

14.0

 

6.5

 

27.1

 

18.9

9.0

38

104

83.1

 

41

 

153

 

110

52

Scroll

Scroll

Scroll

 

Scroll

 

Scroll

 

Scroll

Scroll

1/3-825-2

 

1/3-825-2

 

1/3-825-2

 

1/3-825-2

 

1/3-825-2

1/3-825-2

1/3-825-2

 

 

 

1.3

2.5

2.5

 

1.3

 

2.5

 

2.5

1.3

24" - 2700

24" - 2800

24" - 2800

 

24" - 2800

 

24" - 2800

 

24" - 2800

24" - 2800

 

 

 

 

 

 

 

 

 

 

Blower Motor & Evap.

Blower Motor--HP-RPM-SPD

Blower Motor--Amps

CFM Cooling w/Filter (Wet Coil)

Filter Sizes (inches) STD.

Shipping Weight --LBS.

 

 

 

 

 

 

 

 

 

1/2- Variable

1/2- Variable

1/2- Variable

3/4-Variable

3/4-Variable

3/4-Variable

3/4-Variable

3/4-Variable

3/4-Variable

5.3

5.3

5.3

6.8

6.8

6.8

6.8

6.8

6.8

1100

1100

1100

1500

1500

1500

1700

1700

1700

20x30x2

20x30x2

20x30x2

20x30x2

20x30x2

20x30x2

20x30x2

20x30x2

20x30x2

530

530

530

530

530

530

530

530

530

 

 

 

 

 

 

 

 

 

Form No.

S3378-1112

Supersedes

S3378-712

Page

2 of 12

Page 2
Image 2
Bard WA5S Capacity and Efficiency Ratings, Indoor Blower Performance - CFM 0.00 through 0.80 H2O, Models, WA3S3 WL3S2