2nd Stage Cooling Application Data - Outdoor Temperature 1

2nd Stage Cooling Application Data - Outdoor Temperature 1

Model

D.B./W.B.

Cooling Capacity

50°F

55°F

60°F

65°F

70°F

75°F

80°F

85°F

90°F

95°F

100°F

105°F

110°F

115°F

2

BTU/HR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75/62

Total Cooling

44,125

42,850

41,600

40,325

39,050

37,800

36,550

35,300

34,050

32,800

31,475

30,150

28,825

27,500

 

Sensible Cooling

32,375

31,850

31,300

30,775

30,225

29,700

29,200

28,700

28,200

27,700

27,025

26,350

25,675

25,000

 

 

WA3S3

80/67

Total Cooling

49,150

47,675

46,175

44,675

43,200

41,700

40,125

38,550

36,975

35,400

34,225

33,075

31,900

30,750

WL3S2

Sensible Cooling

32,375

31,800

31,225

30,650

30,075

29,500

28,894

28,300

27,675

27,075

26,625

26,175

25,750

25,300

 

 

85/72

Total Cooling

53,150

51,700

50,250

48,800

47,350

45,900

44,475

43,050

41,625

40,200

38,650

37,100

35,550

34,000

 

Sensible Cooling

32,075

31,550

31,050

30,525

30,025

29,500

29,000

28,500

28,000

27,500

26,925

26,350

25,775

25,200

 

 

 

75/62

Total Cooling

56,025

53,100

51,575

50,050

48,525

48,400

46,950

45,500

44,050

42,600

40,775

38,950

37,125

35,300

 

Sensible Cooling

40,600

40,100

39,450

38,775

38,125

37,300

36,725

36,150

35,575

35,000

34,000

33,000

32,000

31,000

 

 

WA4S3

80/67

Total Cooling

62,725

58,800

56,975

55,150

53,325

53,600

51,700

49,800

47,900

46,000

44,475

42,950

41,425

39,900

WL4S2

Sensible Cooling

41,750

41,300

41,475

39,650

38,800

37,600

36,700

35,800

34,900

34,000

33,450

32,900

32,350

31,800

 

 

85/72

Total Cooling

69,425

66,700

64,800

62,900

61,000

59,900

57,975

56,050

54,125

52,200

50,375

48,550

46,725

44,900

 

Sensible Cooling

41,825

41,500

40,725

39,925

39,150

37,900

37,100

36,300

35,500

34,700

33,975

33,250

32,525

31,800

 

 

 

75/62

Total Cooling

69,350

67,525

65,700

63,900

62,075

60,250

58,425

56,625

54,825

53,000

51,150

49,300

47,450

45,600

 

Sensible Cooling

49,650

48,875

48,100

47,325

46,575

45,800

45,075

44,325

43,600

42,850

41,975

41,075

40,200

39,300

 

 

WA5S3

80/67

Total Cooling

74,750

72,775

70,800

68,800

66,825

64,850

62,775

60,675

58,600

56,500

54,950

53,400

51,850

50,300

WL5S2

Sensible Cooling

48,325

47,550

46,750

45,975

45,175

44,400

43,500

42,600

41,700

40,800

40,475

40,150

39,825

39,500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85/72

Total Cooling

79,375

77,650

75,950

74,225

72,525

70,800

69,275

67,750

66,225

64,700

62,250

59,775

57,325

54,850

 

Sensible Cooling

46,425

45,875

45,350

44,825

44,275

43,750

43,275

42,800

42,325

41,850

41,100

40,325

39,575

38,800

 

 

1st Stage Cooling Application Data - Outdoor Temperature 1

Model

D.B./W.B.

Cooling Capacity

50°F

55°F

60°F

65°F

70°F

75°F

80°F

85°F

90°F

95°F

100°F

105°F

110°F

115°F

2

BTU/HR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75/62

Total Cooling

30,250

29,275

28,300

27,350

26,375

25,400

24,450

23,500

22,550

21,600

20,550

19,500

18,450

17,400

 

Sensible Cooling

22,775

22,300

21,825

21,350

20,875

20,400

19,950

19,500

19,050

18,600

18,025

17,450

16,875

16,300

 

 

WA3S3

80/67

Total Cooling

34,300

33,150

32,025

30,875

29,750

28,600

27,450

26,300

25,150

24,000

22,900

21,800

20,700

19,600

WL3S2

Sensible Cooling

23,075

22,575

22,050

21,525

21,025

20,500

19,975

19,425

18,900

18,350

17,925

17,475

17,050

16,600

 

 

85/72

Total Cooling

37,900

36,700

35,525

34,350

33,175

32,000

30,825

29,650

28,475

27,300

26,125

24,925

23,750

22,550

 

Sensible Cooling

22,400

22,000

21,600

21,200

20,800

20,400

20,025

19,650

19,275

18,900

18,425

17,925

17,450

16,950

 

 

 

75/62

Total Cooling

41,000

39,800

38,660

37,525

36,375

35,300

34,200

33,100

32,000

30,900

29,600

28,300

27,000

25,700

 

Sensible Cooling

29,675

30,000

29,475

28,925

28,400

27,000

26,475

25,950

25,425

24,900

24,325

23,750

23,175

22,600

 

 

WA4S3

80/67

Total Cooling

45,375

43,500

42,225

40,950

39,675

39,000

37,750

36,500

35,250

34,000

32,625

31,250

29,875

28,500

WL4S2

Sensible Cooling

29,875

30,100

29,550

29,000

28,450

27,100

26,550

26,000

25,450

24,900

24,350

23,775

23,225

22,650

 

 

85/72

Total Cooling

51,200

48,100

46,650

45,175

43,725

43,900

42,400

40,900

39,400

37,900

36,600

35,300

34,000

32,700

 

Sensible Cooling

30,625

29,600

29,000

28,300

27,675

27,400

26,725

26,025

25,350

24,650

24,175

23,700

23,225

22,750

 

 

 

75/62

Total Cooling

50,375

49,050

47,725

46,400

45,075

43,750

42,550

41,350

40,150

38,950

37,150

35,325

33,525

31,700

 

Sensible Cooling

37,125

36,575

36,050

35,525

35,000

34,450

33,975

33,500

33,025

32,550

31,775

31,025

30,275

29,500

 

 

WA5S3

80/67

Total Cooling

58,925

56,900

54,900

52,900

50,875

48,850

46,650

44,425

42,225

40,000

38,775

37,550

36,325

35,100

WL5S2

Sensible Cooling

36,900

36,400

35,875

35,375

34,850

34,350

33,450

32,525

31,625

30,700

31,825

32,925

34,050

35,150

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85/72

Total Cooling

62,550

60,800

59,050

57,300

55,550

53,800

52,050

50,275

48,525

46,750

45,050

43,350

41,650

39,950

 

Sensible Cooling

36,250

35,775

35,300

34,825

34,375

33,900

33,475

33,025

32,600

32,150

31,600

30,975

30,400

29,800

 

 

1 Below 50oF, unit requires a factory or field-installed low ambient control. 2 Return air temperature °F.

Clearances Required for Service Access and Adequate Condenser Airflow Intake

MODELS

LEFT SIDE

RIGHT SIDE

WA/L3S, WA/L4S, WA/L5S

20"

20"

 

 

 

Minimum Clearances Required to Combustible Materials

MODELS 1

SUPPLY AIR DUCT

CABINET

FIRST THREE FEET

WA/L3S, WA/L4S, WA/L5S

1/4"

0"

1Refer to the Installation Manual for more detailed information.

Form No.

S3378-1112

Supersedes

S3378-712

Page

10 of 12

Page 10
Image 10
Bard WA5S 2nd Stage Cooling Application Data - Outdoor Temperature, Minimum Clearances Required to Combustible Materials