Typical Sound Performance with Installation/Isolation Curbs & Acoustical Plenums
WA/L3S Sound Data Matrix (dBA @ 10 feet)
| Free Blow Configuration | Ducted Supply Configuration | |||||
|
|
|
| ||||
Unit Mounting | Direct | Isolation | Direct | Direct | Isolation | Isolation | |
|
| Curb |
|
| Curb | Curb | |
|
| WAPFB51 |
|
|
| ||
|
| Free Blow | Standard | Standard | Standard | ||
Supply Air Treatment | Grille | Supply Air | |||||
Supply Air | Supply Duct | Supply Duct | Supply Duct | ||||
|
| Plenum |
|
|
| Silencer | |
|
|
|
|
|
| ||
|
|
| |||||
Return Air Treatment | Grille | Return Air | Grille | Return Air | |||
Silencer | |||||||
|
| Silencer |
| Silencer | |||
|
|
|
|
| |||
Blower Only Operation | 37.8 | 30.7 | 33.6 | 33.6 | 27.4 | 27.6 | |
with CRV | |||||||
|
|
|
|
|
| ||
Compressor Stage 1 | 51.8 | 40.7 | 49.9 | 41.7 | 39.7 | 38.7 | |
Operation with CRV | |||||||
|
|
|
|
|
| ||
Compressor | 52.3 | 41.4 | 50.8 | 42.4 | 40.8 | 39.9 | |
Stage 2 Operation | |||||||
|
|
|
|
|
| ||
Compressor Stage 2 with | 52.7 | 41.7 | 51.7 |
|
| 42.9 | |
ERV High Speed Operation |
|
| |||||
|
|
|
|
|
| ||
Indoor Integrated dBA | 43.8 | 35.0 | 40.7 | 37.2 | 32.8 | 32.6 | |
|
|
|
|
|
|
| |
Compressor Stage 2 | 66.9 | 66.9 | 66.9 | 66.9 | 66.9 | 66.9 | |
Outdoor Sound Level | |||||||
|
|
|
|
|
|
Note 1: dBA is sound pressure measured 10 feet in front of unit and 5 feet above floor.
Note 2: Unit or isolation curb is mounted to frame construction.
Note 3: Results may vary depending upon other factors such as room size, type of construction and acoustical variances.
WA/L4S Sound Data Matrix (dBA @ 10 feet)
| Free Blow Configuration | Ducted Supply Configuration | |||||
|
|
|
| ||||
Unit Mounting | Direct | Isolation | Direct | Direct | Isolation | Isolation | |
|
| Curb |
|
| Curb | Curb | |
|
| WAPFB51 |
|
|
| ||
|
| Free Blow | Standard | Standard | Standard | ||
Supply Air Treatment | Grille | Supply Air | |||||
Supply Air | Supply Duct | Supply Duct | Supply Duct | ||||
|
| Plenum |
|
|
| Silencer | |
|
|
|
|
|
| ||
|
|
|
|
| |||
Return Air Treatment | Grille | Return Air | Grille | Return Air | |||
|
| Silencer |
| Silencer | Silencer | ||
Blower Only Operation | 40.1 | 38.9 | 38.4 | 34.5 | 32.8 | 28.2 | |
|
|
|
|
|
|
| |
Compressor | 52.0 | 41.4 | 50.9 | 41.2 | 40.5 | 39.0 | |
Stage 1 Operation | |||||||
|
|
|
|
|
| ||
Compressor | 53.7 | 44.0 | 52.9 | 44.3 | 42.0 | 40.5 | |
Stage 2 Operation | |||||||
|
|
|
|
|
| ||
Compressor Stage 2 with | 55.0 | 46.2 | 54.0 |
|
| 44.8 | |
ERV High Speed Operation |
|
| |||||
|
|
|
|
|
| ||
Indoor Integrated dBA | 45.4 | 40.4 | 44.0 | 37.8 | 35.8 | 33.0 | |
|
|
|
|
|
|
| |
Compressor Stage 2 | 65.0 | 65.0 | 65.0 | 65.0 | 65.0 | 65.0 | |
Outdoor Sound Level | |||||||
|
|
|
|
|
|
Note 1: dBA is sound pressure measured 10 feet in front of unit and 5 feet above floor.
Note 2: Unit or isolation curb is mounted to frame construction.
Note 3: Results may vary depending upon other factors such as room size, type of construction and acoustical variances.
WA/L5S Sound Data Matrix (dBA @ 10 feet)
| Free Blow Configuration | Ducted Supply Configuration | |||||
|
|
|
| ||||
Unit Mounting | Direct | Isolation | Direct | Direct | Isolation | Isolation | |
|
| Curb |
|
| Curb | Curb | |
|
| WAPFB51 |
|
|
| ||
|
| Free Blow | Standard | Standard | Standard | ||
Supply Air Treatment | Grille | Supply Air | |||||
Supply Air | Supply Duct | Supply Duct | Supply Duct | ||||
|
| Plenum |
|
|
| Silencer | |
|
|
|
|
|
| ||
|
|
|
|
| |||
Return Air Treatment | Grille | Return Air | Grille | Return Air | |||
|
| Silencer |
| Silencer | Silencer | ||
Blower Only Operation | 40.3 | 33.3 | 35.1 | 34.8 | 33.5 | 31.1 | |
|
|
|
|
|
|
| |
Compressor | 52.6 | 40.8 | 50.6 | 43.6 | 40.9 | 39.9 | |
Stage 1 Operation | |||||||
|
|
|
|
|
| ||
Compressor | 56.7 | 45.3 | 51.6 | 46.8 | 44.5 | 43.2 | |
Stage 2 Operation | |||||||
|
|
|
|
|
| ||
Compressor Stage 2 with | 57.8 | 47.1 | 55.0 |
|
| 45.4 | |
ERV High Speed Operation |
|
| |||||
|
|
|
|
|
| ||
Indoor Integrated dBA | 46.2 | 37.2 | 41.8 | 39.0 | 37.2 | 35.4 | |
|
|
|
|
|
|
| |
Compressor Stage 2 | 65.4 | 65.4 | 65.4 | 65.4 | 65.4 | 65.4 | |
Outdoor Sound Level | |||||||
|
|
|
|
|
|
Note 1: dBA is sound pressure measured 10 feet in front of unit and 5 feet above floor.
Note 2: Unit or isolation curb is mounted to frame construction.
Note 3: Results may vary depending upon other factors such as room size, type of construction and acoustical variances.