Beckett AFII Check/Adjust Electrodes, Blower Wheel Replacement, 3/32”, Clamp Screw, 1-1/2”, Stop

Models: AFII

1 20
Download 20 pages 63.93 Kb
Page 17
Image 17
Figure 11a. Electrode Settings-HLX Air Tube

Section: Perform Regular Maintenance

10.If the head was removed when replacing the

Figure 11a. Electrode Settings-HLX Air Tube

nozzle, carefully reconnect the head to the nozzle

Combinations

 

 

adapter. Push the head support until it stops against

 

 

 

the nozzle shoulder. Verify the dimension between

 

3/32”

Do NOT overtighten

the nozzle face and the back of the head is 5/32”.

 

 

 

Clamp Screw

 

 

 

 

1-1/2”

Stop

 

Figure 10a. HLX Air Tube

 

Screw

5/32”

15/32”

1/4”

 

5/32”

SK8263

Nozzle face to back of head

SK9639

Figure 10b. FBX Air Tube

Figure 11b. Electrode Settings-FBX Air Tube

Combinations

SK9461

Check/Adjust Electrodes

Figure 12. – Blower Wheel Replacement

Check the electrode tip settings, as shown in Figure 11a or 11b. If necessary, adjust by loosening the electrode clamp screw and slide/rotate the electrodes as necessary. When the adjustment is complete, securely tighten the clamp screw.

Blower Wheel Replacement

For installation or replacement of a blower wheel, insure that there is a space between the blower wheel and the motor face of 0.062” (1/16” + 1/64”). Refer to Figure 12.

AFII Burner Manual

17

Page 17
Image 17
Beckett AFII Check/Adjust Electrodes, Blower Wheel Replacement, 3/32”, Clamp Screw, 1-1/2”, Stop, 15/32”, Combinations