RS-232485/422 CONVERTERS

Table 2 (continued). DTE Jumper Settings.

Function

Jumper Requirements

 

 

 

9. RS-485 Interface Line Biased (Fail-

S3 Off

No line bias

Safe), Receive

 

 

 

S3 On

Line biased

 

 

 

NOTE

If line bias is on, the RS-485 CD will ALWAYS be on.

3.3 Typical Applications

This section describes some typical applications where the RS-232485/422 Converter might be used. The connections shown in the figures are for the RS-485 port.

Figure 5 shows a typical point-to-point, 4-wire, full- or half-duplex connection with both RS-232485/422 Converters terminated by setting switch S2 to the TERM position. Figure 6 shows a typical point-to-point, 2-wire, half-duplex connection with both RS-232485/422 Converters terminated by setting switch S2 to the TERM position.

In a 4-wire, point-to-point application, each of the drivers on the two RS-232485/422 Converters may always be enabled without any adverse effects.

In a 2-wire, point-to-point or multipoint application, only one driver may be enabled at any one time. If more than one driver is turned ON, a situation known as contention occurs and the data from one driver interferes with the data from the other driver. This results in both sets of data being unintelligible.

22

Page 23
Image 23
Black Box RS-232485/422 Converter Plus, RS-232485/422 Opto-Isolator/Converter, IC109C, IC108A, IC109AE Typical Applications