PROBLEM

 

CAUSE

 

REMEDY

 

 

 

 

 

 

 

 

LOCKOUT:

 

 

 

 

 

Pulsation on start

 

Combustion settings incorrect

 

Set up as in installation instructions

 

 

Faulty nozzle

 

Replace nozzle

Intermittent lockout

 

Bad electrical connection

 

Check control box/electrical connections

 

 

Intermittent flame detection fault

 

See flame detection fault

Burner motor fails to

 

Faulty motor or electrical supply

 

Check for 230v at motor plug during

operate

 

to motor

 

startup period

 

 

Control box fault

 

Replace control box

Flame detection

 

Photocell filmed over (dirty)

 

Wipe clean

fault

 

Photocell faulty

 

Replace

 

 

Control box faulty

 

Replace

Incorrect CO2

 

Air adjustment fault

 

Set up as in installation instructions

 

 

Oil pressure incorrect

 

Set up as in installation instructions

No oil from nozzle

 

No oil at pump

 

Check and refill oil tank/bleed oil line

 

 

 

 

Check and clean filters & valves from oil

 

 

 

 

tank to boiler

 

 

Air in pump

 

Bleed pump

 

 

Nozzle blocked

 

Replace nozzle

 

 

Faulty pump or drive

 

Replace

 

 

Faulty mechanical shut off valve

 

Clean or replace

 

 

(12/18 & 18/25 only)

 

 

 

Ignition failure

 

Electrode settings incorrect

 

Set up as in installation instructions

 

 

Faulty ignition transformer

 

Replace

 

 

Open circuit ignition

 

Check and replace electrodes or high

 

 

 

 

tension leads if necessary

 

 

Faulty control box or electrical

 

Correct control box electrical

 

 

connections not properly made

 

connections or replace control box

 

 

 

 

 

 

BURNER FAILS

 

No power to boiler

 

Check electrical / control circuit

TO START

 

Faulty boiler thermostat

 

Check by temporarily linking out high

 

 

 

 

limit and control thermostats

 

 

Programmer open circuit

 

Check by temporarily linking 8 & 9 on

 

 

 

 

the connector

 

 

Faulty control box

 

Replace

 

 

 

 

 

 

HIGH SMOKE

 

Air intake/flue blocked

 

Check & clear air intake/flue

NUMBER

 

Incorrect combustion settings

 

Set up as in installation instructions

 

 

Oil pressure incorrect

 

Adjust to correct pressure

 

 

Incorrect components used on

 

Check with installation instructions

 

 

combustion head

 

 

 

 

 

Faulty nozzle

 

Replace nozzle

 

 

 

 

 

 

FAULT FINDING

BOILER LOCKOUT :

Indicated by the illumination of the 'Lockout' indicator on the fascia.

To reset, wait 2 minutes then press the lockout reset button.

Also refer to fault finding logic on pages 46 and 47.

FAULT FINDING

& DIAGRAMS

UNDER NO CIRCUMSTANCES MUST AN APPLIANCE BE LEFT TO OPERATE WITH ANY CONTOL LINKED OUT OR OVERRIDDEN.

44

INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32 8 716 106 252b (07/06