![User (Passcode) Worksheet (Users 000 to 029)](/images/new-backgrounds/50060/5006021x1.webp)
D1255RB/D1256RB/D1257RB Installation Instructions 4.0 D1256RB Programming Requirements
4.4.1Menu Item and Function
Program the first ten menu items as indicated in Table 3. This programming is necessary for the D1256RB to operate properly. The first four keys on the D1256RB execute the first four menu items enabled at the keypad address. Menu items five through ten are optional features that can be programmed into the D1256RB system. Refer to the Fire System User’s Guide (P/N: F01U011793) for further explanation of these optional programmable items.
Ensure that CF 128 through CF 131 are programmed E (enabled) and not P (passcode required).
Table 3: | Function List Description | |
|
|
|
|
|
|
Menu Item | Function | Description |
1 | 128 | ALARM SILENCE? |
2 | 129 | TROUBLE SILENCE? |
3 | 130 | DETECTOR RESET? |
4 | 131 | ANNUNCIATOR RESET |
|
|
|
5 | 9 | VIEW MEMORY? |
6 | 10 | VIEW PT STATUS? |
7 | 12 | FIRE TEST? |
8 | 21 | VIEW LOG? |
9 | 29 | REMOTE PROGRAM? |
10 | 32 | DISPLAY REV? |
|
|
|
4.4.2CC Address #
CC = command center = keypad
Program the keypad (command center) addresses as Yes for the first four menu items and for the optionally programmed menu items five through ten.
4.4.3Passcode Worksheet
Figure 17: Example – Fire Passcode Worksheet
User (Passcode) Worksheet (Users 000 to 029)
User | User |
|
| Area Authority |
|
|
| |||||
## |
|
|
|
|
|
|
|
|
|
| ||
Passcode | Group | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | User Name | ||
# | ||||||||||||
|
|
|
|
|
|
|
|
|
| |||
000 | 123 __ __ __ __ __ __ | ____ | 15 | 15 | 15 | 15 | 15 | 15 | 15 | 15 | SERVICE | |
PASSCODE | ||||||||||||
|
|
|
|
|
|
|
|
|
|
| ||
001 | 1 2 5 6 0 0 | ____ | 14 | __ | __ | __ | __ | __ | __ | __ | USER 1 |
Refer to User (Passcode) Worksheet in the program record sheet for the control panel.
4.4.4Passcode
A special passcode must be programmed as a valid passcode for the system to work properly. This passcode is used in Custom Functions 128 through 131. Use any user number to establish this mandatory valid passcode. You must also create it as a valid passcode in the area to which the D1256RB is assigned. Use Authority Level 14 together with the passcode you select. Ensure that Passcode Arm is disabled (blank) for the Authority Level. Refer to Authority Level Selections in the program record sheet for the control panel.
Bosch Security Systems, Inc. 8/06 F01U011791B | 11 |