Bosch Appliances D2071A manual Program Modules, Editing the Program Record

Models: D2071A

1 28
Download 28 pages 23.82 Kb
Page 20
Image 20

D2071A Operations & Installation Guide 4.0 Program Record

3.8Program Modules

Unlike larger Bosch products, the D2071 Product Handler does not group program items in program modules. When you enter the 2071 program, you are in the Program Item Level.

3.9Editing the Program Record

Each D2071A DACT programming option is listed as it appears in the Programmer Display. The default, a set of selections, and a description follows.

The selections are the only entries available for a particular program option. For example, Account # only uses numbers 0 through 9, letters B through F, or no entry. Do not use unlisted entries.

To edit program options, change the entry and press [ENTER]. If the entry is valid, the programmer moves the cursor to the next prompt. When all program options in the record are edited, the programmer returns to the first program option in the record.

You can exit from any point within the program by pressing [EXIT GROUP] until PRODUCT HANDLERS appears on the D5200 Programmer.

4.0Program Record

The 2071 Program Record selects several functions of the D2071A DACT, including the account number that:

identifies the location during communication,

decides how the telephone number is dialed,

determines how the D2071A is powered, and

controls the loop response times.

Account #

Default:

 

Blank

 

 

 

Selections:

 

0 to 999, BBB to FFF, or Blank

 

 

 

Ensure all entries are right-justified. The blank entry, equaling no account number, sends 000 in pulse that sends nothing in the BFSK format.

Transmit BFSK

Default:

Yes

 

 

Selections:

Yes or No

 

 

Yes

Transmit in BFSK format with

 

2300 Hz acknowledgement.

 

 

No

Transmit in fast, single-round,

 

expanded pulsed format with a

 

checksum digit and 2300 Hz

 

acknowledgement.

 

 

Use to select the reporting format.

DTMF Dialing

 

Default:

 

Yes

 

Selections:

 

Yes or No

 

Yes

 

Dual tone multi-frequency dialing of

 

 

 

telephone numbers.

 

 

 

 

 

No

 

Pulse dialing of telephone numbers.

 

 

 

 

 

 

PriPre

 

 

 

 

 

 

 

 

Default:

 

Blank

 

 

 

Selections:

 

0 to 9, B to F, or Blank

 

 

 

Blank

No prefix or area code. A delay up

 

 

to 7 sec is automatically inserted in

 

 

front of the prefix.

 

 

 

 

Use to select the prefix for the primary receiver telephone number. You can enter up to nine characters. Refer to Table 9 on page 21 for other dialing character selections.

2 0

Bosch 09/04 74-06200-000-F

Page 20
Image 20
Bosch Appliances D2071A manual Program Modules, Editing the Program Record