D2071A Operations & Installation Guide 1.0 Overview

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 1: Required Materials

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Item

 

 

Description

 

 

 

 

 

 

 

 

D126 Battery

 

Use a 12 V, 7 Ah battery for NFPA 72 remote station stand-alone applications. Must

 

 

 

 

 

 

 

provide 60 h of standby plus 5 min of alarm operation. Use only in 12 VAC Mode.

 

 

 

D129 Battery

Only use 12 V, 2.3 Ah battery for NFPA 72 central station applications. Must provide

 

 

 

 

24 h of standby. Use only in 12 VAC Mode.

 

 

D136 Relay 1 or 2 (optional)

 

Use one relay to enable the Phone Line Trouble Relay (K5) and use the other relay to

 

 

 

 

 

 

 

enable the Initiating Circuit Alarm Relay (K6).

 

 

 

D161* or D162 Phone Cord (2)

 

Primary and alternate telephone line connections.

 

 

 

 

 

 

 

D1220

Transformer

 

Use only in 12 VAC Mode.

 

 

 

D4103R Enclosure ** or

Use either enclosure or another UL Listed fire enclosure.

 

D8109

Enclosure (optional)

 

 

 

 

 

 

D2002

Mounting Plate* (optional)

 

Use to mount the D2071A in a D4103 Enclosure.

 

 

 

D5100

Programmer or

Use either programmer with the 2071 Product Handlers loaded.

 

D5200 Programmer

 

 

 

 

 

D8004

Transformer Enclosure

Required for the D1220 Transformer in commercial fire applications if the D2071A Kit

 

 

 

 

is not used.

 

* You must use the D8004 Transformer Enclosure or the D2071AC for commercial fire applications.

1.5.1Mandatory Connections

To comply with the NFPA 72 Central Station Fire or NFPA 72 Remote Station Signaling Service, connect the D2071A as described in Table 2. The Class “A” and Class “B” circuits are mandatory connections for the slave and stand-alone applications. Refer to Section 2.0 Installation on page 8 for wiring instructions.

Table 2: Mandatory Connections for the NFPA 72 Central Station and Remote Station

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Stand-Alone Applications

 

Slave Applications

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Connection

 

Terminal

NFPA 72

 

NFPA 72

 

NFPA 72

 

NFPA 72

 

 

Number

Central Station

 

Remote Station

 

Central Station

 

Remote Station

12 VAC Primary Power*

 

1, 2

 

OK

 

OK

 

 

OK

 

OK

 

24 VDC Primary Power

 

1,2

 

NO

 

NO

 

 

OK

 

OK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D126 Battery Backup

 

4, 5

 

OK

 

Required

 

 

OK

 

Required

 

(12 VDC, 7Ah)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D1219 Battery Backup

 

4,5

OK

 

NO

 

 

OK

 

NO

(12 VDC, 2.3 Ah)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Class “A”, Style D Circuit

 

6, 7, 8, 9

 

Maximum of 5 waterflow switches or up

 

 

Normally open dry alarm output

 

 

 

 

to 100 mechanically activated initiating

 

 

contacts of an existing FACP.

 

 

 

 

devices such as heat detectors or

 

 

 

 

 

 

 

 

 

 

 

 

 

manual pull stations. Not suitable for

 

 

 

 

 

 

 

 

 

 

 

 

 

smoke detectors.

 

 

 

 

 

 

 

 

 

 

 

 

Retard and Reset Times

 

6, 7, 8, 9

Refer to the appropriate standard or as

 

N/A

 

 

 

 

 

(waterflow alarm only)

 

 

allowed by the AHJ.

 

 

 

 

 

 

 

 

 

 

 

 

Class “B”, Style A Circuit

 

6, 7, 8, 9

 

3

 

 

 

3

 

 

3

 

 

 

 

3

 

(recommended mode)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10, 11

Monitors up to 20 valve supervisory

 

Normally open dry trouble contacts of

 

 

 

switches per circuit.

 

 

 

 

an existing FACP.

 

 

 

 

 

 

 

11, 12

 

Mode 1 is not acceptable.

 

 

Mode 3 is preferred.

 

 

 

 

Mode 2 is only acceptable when a valve

 

 

Modes 1 and 2 are acceptable.

 

 

 

 

tamper device, with only a normally

 

 

 

 

 

 

 

 

 

 

 

 

 

closed contact, must be used and only

 

 

 

 

 

 

 

 

 

 

 

 

 

on approval of the AHJ.

 

 

 

 

 

 

 

 

 

Earth Ground

 

3

 

Yes

 

 

 

 

 

No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*You must use the D8004 Transformer Enclosure or the D2071AC for commercial fire applications.

Bosch 09/04 74-06200-000-F

5

Page 5
Image 5
Bosch Appliances D2071A manual Required Materials, Mandatory Connections

D2071A specifications

The Bosch Appliances D2071A is an exemplary appliance that enhances everyday cooking and food storage with its premium features and stylish design. This model stands out in the Bosch lineup for its innovative technologies designed to provide optimal performance while ensuring user-friendly operation.

One of the main characteristics of the D2071A is its energy efficiency. Bosch has integrated advanced technologies that comply with the highest energy standards, which not only help reduce electricity bills but also promote environmental sustainability. The appliance operates with minimal energy consumption, making it a great choice for eco-conscious consumers.

The D2071A boasts a sleek and modern design that can seamlessly fit into any kitchen decor. With its stainless steel finish, it offers durability as well as an elegant appearance. The appliance is designed with a seamless integration feature, allowing it to blend in with cabinetry, giving a built-in look that is favored by many homeowners.

In terms of performance, the D2071A features advanced cooling technologies that ensure optimal temperature control and food preservation. With a multi-air flow cooling system, cold air is distributed evenly throughout the fridge and freezer compartments, preventing hot spots that can compromise food quality. This technology ensures that perishables stay fresher for longer periods, minimizing waste.

Another notable feature is the adjustable shelving and storage options. The D2071A includes customizable shelving that can be rearranged to accommodate various food items and containers. This flexibility allows users to maximize storage space, making it easy to store everything from tall bottles to wide platters.

The appliance is equipped with intuitive controls and a user-friendly interface. This allows for easy temperature adjustments and access to various settings that enhance the user experience. Additionally, the D2071A comes with a notification system that alerts users in case of temperature fluctuations, helping to maintain food safety.

Overall, the Bosch Appliances D2071A combines modern design with cutting-edge technology, making it a top choice for individuals looking for a high-quality refrigerator. It successfully merges functionality, efficiency, and style, thus catering to the diverse needs of today’s home cooks and families.