D2071A Operations & Installation Guide 2.0 Installation
2.0Installation
Some terminals are wired differently for the
When you are using the D2071AC, mount the D4103R Enclosure and have a qualified electrician connect a 110 VAC or 120 VAC power source to the black and white leads on the transformer. Before beginning the D2071A installation, ensure the power source is turned off.
Figure 2: Stand-Alone Installation
10
P 10
S 11
1 | S | P |
| 1 | 12 VAC, 20 VA, 60 Hz |
|
|
| |||
|
|
| 2 | 12 VAC, 20 VA, 60 Hz | |
| S | P |
| ||
|
|
|
| 3 | EARTH GND |
3 |
| - | P | 4 | BATTERY – |
| + |
| 5 | BATTERY + | |
|
| P | |||
5 | P |
|
| 6 | INITIATING A1 – |
|
|
|
|
| |
| S |
|
| 7 | INITIATING A2 – |
| 6 |
|
| 8 |
|
5 | P |
|
| INITIATING B1 + | |
|
|
| 9 | INITIATING B2 + | |
| S |
|
| ||
9 |
| 8 |
|
|
|
P |
|
|
|
| |
|
|
| 10 | SUPERVISORY HI | |
| 10 |
|
| ||
P |
|
| 11 | SUPERVISORY LO | |
| S |
|
| ||
S | 11 |
|
| 12 | SUPERVISORY HI |
| P |
|
| ||
11 | 11 | NC | 13 | TBL RELAY NC | |
|
|
| |||
|
| C |
| 14 | TBL RELAY COM |
|
|
|
| ||
|
| NO | 15 | TBL RELAY NO | |
|
| NC |
| 16 | ALARM RELAY NC |
|
| C |
| 17 | ALARM RELAY COM |
|
|
|
| ||
|
| NO | 18 | ALARM RELAY NO |
2
4
7
12
13
1 - 12 VAC, 20 VA transformer
2 - Maximum charging current 300 mA
3 - Battery backup (D126 [12 V, 7 Ah] or D1219 [12 V, 2.3 Ah])
4 - Alarm initiating circuit
5 - Open = Trouble
6 - Short = Alarm
7 - Supervisory circuits
8 - Mode 3 (Alarm [short] = 0 VDC to 1.7 VDC; Normal [resistive] = 1.9 VDC to 5.8 VDC; Trouble [open] = 6.0 VDC to 10.2 VDC)
9 - Mode 2 (Normal = 0 VDC to 1.5 VDC; Alarm [resistive] = 1.8 VDC to 9.0 VDC; Trouble [open] = 9.3 VDC to 13.0 VDC)
10 - Mode 1 (Normal = 0 VDC to 1.5 VDC; Alarm [open] = 1.8 VDC to 13.0 VDC)
11- 1.8 kΩ EOL resistor
12- Phone Trouble Relay (maximum rating 2 A at 30 VDC)
13- Initiating Circuit Alarm Relay (maximum rating 2A at 30 VDC)
Note: = Power limited;
= Supervised