Bosch Appliances F220-B6 installation manual Set Detector Modes, Test Mode, Sensitivity Mode

Models: F220-B6

1 28
Download 28 pages 11.75 Kb
Page 21
Image 21

F220 Series Detectors with F220-B6/C/E/R Bases

Install the Detector Heads en 21

 

 

4.2Set Detector Modes

The F220 Series Smoke Detectors feature a unique magnet-operated sensitivity mode and detector test mode.

4.2.1Test Mode

Test the detector by placing the magnet next to the T mark on the mounting skirt (refer to Figure 4.2, Item 8 on page 19) for three consecutive flashes to cause an alarm.

4.2.2Sensitivity Mode

If the magnet is next to the T mark for less than three flashes but more than one flash, the detector enters Sensitivity Mode.

1.Place the detector into Sensitivity Mode.

2.Wait for the first single green LED flash.

3.Count the number of red LED flashes that follow and refer to Table 4.1 for sensitivity definitions.

Number of

Sensitivity Definition (% Obscuration)

Red Flashes

 

 

 

1

Malfunctioning smoke or heat detector

 

 

3

Normally operating smoke or heat detector with

 

little or no dirt contamination

 

 

4 to 6

Progressively more contamination

 

 

7 to 10

Trouble condition, very dirty but still

 

compensated to 3%/ft (3%/ft = 0.433 db/m);

 

Sensitivity < 3%/ft at 10 flashes.

 

 

11

Sensitivity < 2.5%/ft (2.5%/ft = 0.36 db/m)

 

 

12

Sensitivity < 2.0%/ft (2.0%/ft = 0.287 db/m),

 

chance of false alarm increases

 

 

13

Sensitivity < 1.5%/ft (1.5%/ft = 0.214 db/m)

 

 

14

Sensitivity < 1.0%/ft (1.0%/ft = 0.143 db/m),

 

chance of false alarm greatly increases

 

 

15

Sensitivity < 0.5%/ft (0.5%/ft = 0.071 db/m),

 

false alarm likely

 

 

Table 4.1 Red LED Flash Definition

4.The detector exits sensitivity mode and returns to one green LED flash every eight seconds.

Bosch Security Systems, Inc.

Installation Manual

4998138694 -04 2007.01

Page 21
Image 21
Bosch Appliances F220-B6 installation manual Set Detector Modes, Test Mode, Sensitivity Mode